Suspension Bolts Layout and Ceiling Opening
Using the installation template, remove and/or modify the ceiling panels and install suspension bolts as in the images
below.
1102 x 446: Dimensions for opening
1010.4 x 280.4: Suspension Bolts
Mark position of field supplied suspension rods, water lines, condensate drain pipe, line voltage and low voltage wiring.
Properly attach suspension rods to structure above.
Do not tighten nuts and counter nuts. This should only be done after all connections are made and leveling of unit is
confirmed.
Verify installation accommodates proper condensate drainage to pump.
Be careful while lifting fan coil unit into position. Do not lift the unit by condensate tray.
Counternut
Washer
NUT
Rod
Nut