Page
33
of 61
SK2019 FCSD 1V-01-EC-001_1
Without Valve Configuration
COOL MODE
a)
Electric heater, AUX1, MTV1 and MTV2 are always off.
b)
If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated and AUX2 is turned on. Indoor
fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated and AUX2 is turned off. Indoor fan runs at Modbus 310000 setting.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Note: When the unit is turned off, the indoor fan shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1 ≤ 2ºC for 2 minutes, then AUX2 is turned off. If low speed is selected via user interface, then indoor fan runs at
medium speed. If medium or high speed is selected via user interface, then indoor fan runs at set speed.
b)
If Ti1 ≥ 5ºC for 2 minutes, then AUX2 is turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, AUX1, AUX2, MTV1 and MTV2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Heat mode without electrical heater
a)
MTV1, MTV2, AUX2 and heater are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and AUX1 is turned on. Indoor fan
runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and AUX1 is turned off. Indoor fan runs at 200rpm.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Heat mode with electrical heater as booster
a)
MTV1, MTV2 and AUX2 are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and AUX1 is turned on. Indoor fan
runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and AUX1 is turned off. Indoor fan runs at Modbus 310000 setting.
d)
If Ti1 < 40ºC, then the electrical heater is turned on. If 40ºC ≤ Ti1 < 45ºC, then the electrical heater maintains its original
state. If Ti1 ≥ 45ºC, then the electrical heater is turned off.
e)
The range of Ts is 16 - 30ºC.
f)
Indoor fan speed can be adjusted to low, medium, high and auto.
PRE-HEAT
Pre-heat with electrical heater
a)
Indoor fan will start after the electrical heater has been turned on for 10s.
POST-HEAT
Post-heat with and without electrical heater
a)
AUX1 is off. Electrical heater is turned off.
b)
Indoor fan will stop after the unit has been turned off for 20secs.