Page
35
of 61
SK2019 FCSD 1V-01-EC-001_1
Control Logic For 4-Pipe System
Note: 4-pipe system must always be equipped with 2 valves.
COOL MODE
a)
MTV2, AUX1 and Electrical Heater are always off.
b)
If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated, MTV1 and AUX2 are turned on.
Indoor fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated, MTV1 and AUX2 are turned off. Indoor fan runs at set speed.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV1 requires 30 seconds before it is fully open.
g)
When turned off, MTV1 requires 120 seconds before it is fully closed.
h)
When the unit is turned off, the indoor fan will shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1 ≤ 2ºC for 2 minutes, then MTV1 and AUX2 are turned off. If indoor fan is set for low speed, then it will run at
medium speed. If it is set at medium or high speed, then it will keep running at the same speed.
b)
If Ti1 ≥ 5ºC for 2 minutes, then MTV1 and AUX2 are turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Without Electrical Heater
a)
MTV1, AUX2 and are heater always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated, MTV2 and AUX1 are turned on.
Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan runs at Modbus 310000 setting.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
f)
When turned on, MTV2 requires 30 seconds before it is fully open.
g)
When turned off, MTV2 requires 120 seconds before it is fully closed.
With Electrical Heater as Booster
a)
MTV1 and AUX2 are always off.
b)
If Tr ≤ Ts - 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated, MTV2 and AUX1 are turned on.
Indoor fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated, MTV2 and AUX1 are turned off. Indoor fan runs at Modbus 310000 setting.
d)
If Ti2 < 40ºC, then the electrical heater is turned on. If 40ºC ≤ Ti2 < 45ºC, then the electrical heater maintains its original
state. If Ti2 ≥ 45ºC, then the electrical heater is turned off.
e)
The range of Ts is 16 - 30ºC
f)
Indoor fan speed can be adjusted to low, medium, high and auto.
g)
When turned on, MTV2 requires 30 seconds before it is fully open.
h)
When turned off, MTV2 requires 120 seconds before it is full closed.