7
Installation for 230V Screens
RJ-45
Receptacle
RJ-22
Output
RJ-22
Inputs
Up (Dry Contact)
Down (Dry Contact)
Common (Both)
Bus (Bus)
5V (Bus)
UP
STOP
DOWN
BUS
C
O
M
5
V
Front of
Wall Switch
Bus
UP
STOP
DOWN
BUS
C
O
M
5V
LED
Up Limit
Tactile Button
Down Limit
Tactile Button
Back of
Wall Switch
RJ-22 Pin-Outs
(Tab Is Facing Down)
Standard RJ-22 can be used in place of RJ-14 cable
Bus (RP Data)
+12V
RQ Clock
RQ Data
+5V
Ground
Yellow
Red
Green
Black
White
Blue
RJ-45 Pin-Outs
(Tab Is Facing Down)
+12V
Manual 2
Ground
Manual 1
RQ Clock
Bus (RP Data)
RQ Data
+5V
Blue
Green
Yellow
Red
Black
Orange
Purple
Brown
230V Wiring Diagram with Operation & Limit Adjustment
Wall Switch
3-conductor 20–24 gauge wire can be used in place of the
supplied RJ-14 cable to connect the wall switch. Connect the BUS
terminals on the wall switch to the corresponding BUS terminals
on the splitter board.
IMPORTANT NOTE:
The wall switch is REQUIRED to make any
limit switch adjustments, EVEN if a third party control system is
used. Therefore, it is advised to wire the switch or provide a
3-conductor connection that is accessible.
UP
STOP
DOWN
BUS
C
O
M
5V
Power Input 230VAC / 50Hz
Green / Yellow (Ground)
Blue
(Hot)
Brown
(Common)
Power
Wire
Data
Cable
RJ-45 Jack
RJ-22 Jack
(Connection to
Wall Switch)
RJ-22
Jack
RJ-14 Pin-Outs
(Tab Is Facing Down)
Supplied RJ-14 cable
Bus (RP Data)
RQ Data
+5V
Ground
White
Green
Red
Black