Electrical Installation

1.   Open the junction box on the left end of the case using a  

#2 Phillips screwdriver. Install electrical connections that 
apply to your unit. Make sure to review the wiring diagram 
for proper hook up. Replace the junction box cover.

 

NOTE:

 Must be installed in accordance with the 

requirements of the Local Building Codes, the Canadian 
Electrical Code (CEC), CAN/CSA C22.1 and the National 
Electric Code (NEC), NFPA 70.

2.  Test installation by running screen up and down a few times. 

Be prepared to stop screen should any objects obstruct the 
movement of the screen. To prevent damage to the motor, 
the standard duty cycle is 1 minute on and 3 minutes off.

Figure 5

Junction 
Box Cover

Installation (continued)

Ceiling Hook Bracket

1/4 X 5/8"  
Flat Head Screw

Figure 4

Ceiling Hook Mount

1.   The ceiling hook mount brackets are tied together and 

attached to the ceiling flush mount bracket at one end of 
the case. Remove the ceiling hook mount brackets. 

2.   Remove the ceiling flush mount brackets using a #2 Phillips 

screwdriver. See Figure 3. Retain four 1/4”x 5/8” screws.

 

NOTE: 

Do not remove the wall mount bracket, even if you 

are  
not using it for mounting. This provides structural stability  
to the case. 

3.   The top of the screen case has two channels with threaded  

nuts that slide the length of the case. Attach the two ceiling  
hook mount brackets using the 1/4”x 5/8” screws and 
threaded nuts, two per bracket. The brackets can be 
attached anywhere within 12" of the ends of the case (Figure 
4).

4.   Before hanging your Tensioned Contour Electrol, be sure  

the ceiling has adequate reinforcement.

5.   Using the holes in the ceiling hook brackets, hang the  

Tensioned Contour Electrol using the appropriate hardware  
and fasteners for your ceiling type.

Summary of Contents for TENSIONED CONTOUR ELECTROL

Page 1: ...INSTRUCTION BOOK FOR Tensioned Contour Electrol ...

Page 2: ...nce with the wiring rules 4 Rated for indoor use only 5 Use copper rated conductors rated 167 F 75 C or higher 6 If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid hazard 7 Supplied drive is only intended for use in Da Lite screen models Advantage Contour and Cosmopolitan 8 Position the cord so that it will not b...

Page 3: ...ket 5 Tighten the two stop screws against the wall mount bracket using a 2 Phillips screwdriver Figure 1 Ceiling Flush Mount 1 The ceiling hook brackets are attached to the top side of the housing They must be removed prior to ceiling flush mount NOTE Do not remove the wall mount bracket even if you are not using it for mounting This provides structural stability to the case 2 Using a 2 Phillips s...

Page 4: ...gure 4 Ceiling Hook Mount 1 The ceiling hook mount brackets are tied together and attached to the ceiling flush mount bracket at one end of the case Remove the ceiling hook mount brackets 2 Remove the ceiling flush mount brackets using a 2 Phillips screwdriver See Figure 3 Retain four 1 4 x 5 8 screws NOTE Do not remove the wall mount bracket even if you are not using it for mounting This provides...

Page 5: ...20 24 gauge wire can be used in place of the supplied RJ 14 cable to connect the wall switch Connect the BUS terminals on the wall switch to the corresponding BUS terminals on the splitter board IMPORTANT NOTE The wall switch is REQUIRED to make any limit switch adjustments EVEN if a third party control system is used Therefore it is advised to wire the switch or provide a 3 conductor connection t...

Page 6: ...k Orange Purple Brown 220V Wiring Diagram with Operation Limit Adjustment Wall Switch 3 conductor 20 24 gauge wire can be used in place of the supplied RJ 14 cable to connect the wall switch Connect the BUS terminals on the wall switch to the corresponding BUS terminals on the splitter board IMPORTANT NOTE The wall switch is REQUIRED to make any limit switch adjustments EVEN if a third party contr...

Page 7: ...switch is for operation only and CANNOT be used to make limit switch adjustments Therefore it is advised to wire the limit adjustment switch or provide a 3 conductor connection that is accessible Power Input 220VAC 50Hz Green Yellow Ground Blue Hot Brown Common Power Wire Data Cable RJ 45 Jack Black Down White Common Red Up Red Black White Inputs Output Black Down White L Common Red Up Push Down o...

Page 8: ... from the projector s 5 or 12 volt screen trigger output to the length required to reach the VPI NOTE When extending the low voltage connection from the projector s screen trigger output polarity does not matter The red and black wires from the VPI are interchangeable IMPORTANT NOTE The wall switch is REQUIRED to make any limit switch adjustments EVEN if a third party control system is used Theref...

Page 9: ...ch will turn off the motor will return to run mode and no changes will be saved If this occurs return to step 3 for down limit adjustment or step 4 for up limit adjustment NOTE All screens except Parallax standard with 12 black drop at the top Screens with Parallax surface standard with 2 of black drop at the top 4 To adjust the up limit switch press and hold the up tactile button until the LED on...

Page 10: ...ure across the common up and down wires will be a stop command Operation of Screen Operation Limit Adjustment Wall Switch 1 Press DOWN button on screen switch and screen will deploy out of case in downward direction 2 Press STOP button on screen switch and screen will stop if in movement 3 Press UP button on screen switch and screen will retract upward into case Up Button Stop Button Down Button U...

Page 11: ...Defective motor limit switch or capacitor Replace motor assembly NOTE Motor is a sealed assembly Capacitor burned out Replace motor assembly Incorrect stopping position in downward direction Lost roller wrap See instructions below Down limit switch out of adjustment See installation instructions Incorrect stopping position in upward direction Lost roller wrap See instructions below Up limit switch...

Page 12: ...RRANTIES EXPRESS OR IMPLIED INCLUDING WARRANTIES AS TO FITNESS FOR USE AND MERCHANTABILITY Any implied warranties of fitness for use or merchantability that may be mandated by statute or rule of law are limited to the five 5 year warranty period This warranty gives you specific legal rights and you may also have other rights which vary from state to state TO THE MAXIMUM EXTENT PERMITTED BY APPLICA...

Reviews: