At the end of pump startup (as described in par. 5.2), the flow is checked; if it regular, Priming has already been 
completed and it passes to the conditions of the active setpoint. 

 

 

If this is not the case, the system has discharged and must be primed again: it now enters the second phase, 
where the pump is activated at 

Maximum Priming Speed

, until it is primed or at any rate for all the time specified 

by the parameter “

Max Priming Time

”. 

 

Here too, if priming has been successful, it proceeds regularly according to the active setpoint.  
But if priming has not been successful, it goes into “

NoPriming

” fault status (block). On blocks and resets, see chapter 

7. 

 

Figure 36 

 
The “

Priming

” item on the menu allows you to: 

 

enable or disable the function (factory value: enabled);

 

 select 

Max Priming Speed

”, between 50% and 100%; 

 

select “

Max Priming Time

”,  between 1 and 30 minutes. 

 

 
The factory values are given in chapter 8. 

 

In installations below water level, it is not generally necessary to perform Priming each time the pump is 
started (and it can be disabled). 
The maximum speed during priming (“Max Priming Speed”) can be reduced in the case of systems that 
are not able to withstand high speeds.

 

 

6.2.8  Antifreeze (Protection against water freezing in the pump) 

As is known, the formation of ice, that is the change of state of water from liquid to solid, causes an increase in 
volume, with the risk of breakages for the systems containing water.  
For this reason it is generally recommended to empty any pump and hydraulic system during winter, when the 
temperatures are close to freezing point.  
 
However, our system is equipped with the “

Antifreeze

” function, which automatically rotates the pump if the 

temperature falls to values close to zero. The water inside the pump is thus kept moving and slightly heated, thus 
limiting the risk of the formation of ice. 
 

 

This function protects the pump, but it cannot generally prevent the formation of ice in the swimming 
pool or in other parts of the system. 

 

The temperature sensor is fitted close to the motor and does not directly feel the water temperature, but 
that of the pump motor assembly. 
If the pump is in a technical room, the outdoor temperature may be lower, even much lower, than the 
one measured by the sensor.

 

 

ATTENTION: The 

Antifreeze

 protection works only as long as the system is regularly powered: with the 

electric power disconnected or in the absence of current (even accidental, such as after a blackout) the 
protection cannot work. So it is advisable not to leave the system loaded during periods of inactivity in 
winter, but empty it accurately. 

 

In cases of long inactivity, it is advised not to disconnect the electric power to keep the 

antilock

 

protection active (see the following paragraph). 

 

The intervention of the Antifreeze function turns the pump even if the system is in STOP status (white 
led 

 blinking), and is not influenced by the active operating mode (manual or automatic). 

 

If you want to prevent the Antifreeze function intervening and turning on the motor, the function 
must be disabled.

 

 

Summary of Contents for E.SWIM

Page 1: ...INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE E SWIM E PRO...

Page 2: ...e and opening page of the menu 47 6 1 2 Access to a sub menu 47 6 1 3 Changing a parameter in the menu 48 6 2 Menu structure 50 6 2 1 Settings 51 6 2 1 1 WIZARD loaded from the menu 51 6 2 1 2 Languag...

Page 3: ...cal qualifications required by the specific legislation in force The term skilled personnel means persons whose training experience and instruction as well as their knowledge of the respective standar...

Page 4: ...of safety precautions in accordance with the regulations in force in the country where the product is installed for Italy CEI 64 2 All repair and maintenance work must be carried out only after havin...

Page 5: ...person especially a child covers the drain with his body he could be trapped and held under water until he drowns There could be the same tragic outcome if long hair were caught in the drain trapping...

Page 6: ...or errors in copying The Manufacturer reserves the right to make any modifications to products that it may consider necessary or useful without affecting their essential characteristics 1 GENERAL 1 1...

Page 7: ...aximum working pressure 2 5 bar WORKING CONDITIONS Max liquid temperature 40 C 104 F Max ambient temperature 50 C 122 F Table 1 Technical Characteristics 2 INSTALLATION The system must be used prefera...

Page 8: ...ut by an expert authorised electrician who takes on all responsibility The system must be correctly and safely earthed as required by the regulations in force The mains voltage must be the same as tha...

Page 9: ...contact are described in paragraph 6 2 6 2 The following inputs are available see also par 6 2 6 1 1 A digital input with clean contact maximum voltage 5Vdc maximum current 1mA the closed contact mean...

Page 10: ...yboard and Display Figure 6 Description of the elements 1 LCD graphic screen 2 Six LED warning light indicating the active function each LED indicates the activation of the key next to it 3 LED red wa...

Page 11: ...if a mode is active that contemplates switching on at the current moment In STOP condition when the white LED is blinking the pump can never stop until RUN STOP is pressed The only exceptions the Anti...

Page 12: ...ry open to let the air out Figure 8 Installation above water level If there are several suction pipes arrange the pipes and the manifold below water level and reach the pump with only one vertical pip...

Page 13: ...in the first position and the sign on the bar is at the top the keys to use are indicated at the bottom as well as the arrows which for simplicity are not shown o OK key confirms any changes made and...

Page 14: ...aditional pumps Generally when the work point falls below the maximum curve the system reduces the absorbed power and thus decreases the energy consumption 5 1 2 Command modesThe system can operate in...

Page 15: ...duration by means of the menu see 6 2 2 Also the operation associated with the QuickClean key can be customized see 6 2 4 Pressing a SETx or QuickClean key puts the pump into Manual mode which has pre...

Page 16: ...6 In this case the internal timers do not intervene These two modes make up the Auto mode It is disabled when the pump leaves the factory because it must be configured specifically for each system swi...

Page 17: ...are positioned is highlighted by the flashing box dotted in the figure The previous menu item at the top and the next item at the bottom are also shown 4 The line at the bottom indicates which keys ca...

Page 18: ...As well as the complete menu structure paragraph 6 2 also shows the branch and item numbering of all the parts of the menu 6 1 3 Changing a parameter in the menu Let us see how to change the value of...

Page 19: ...xample we confirm by pressing OK and leave the hour and minute setting as shown in the following figure Instead if we want to abandon the changes made we press ESC to return to the figure in point 1 F...

Page 20: ...1 Preferences 1 6 Password 1 PW set reset 1 7 Set Points 1 4 SP1 4 settings 2 Set Points 5 8 SP5 8 settings 3 Quick Clean Quick Clean set 4 Timers Menu Timers 5 Configuration 5 SP select start stop 5...

Page 21: ...22 The choice is made by selecting the desired language with the up arrow and down arrow keys and pressing OK The factory setting is given in chapter 8 6 2 1 3 Day Time From this page we set the curre...

Page 22: ...backlight time counted from the last time a key was pressed The backlight time can vary from 20 sec to 10 min or it may be always When the backlight is off the first time any key is pressed has the s...

Page 23: ...k the device 6 2 2 Set Points 1 4 The parameters associated with the keys from SET1 to SET4 can be viewed and changed under this menu item through the page shown on the screen Figure 27 The first choi...

Page 24: ...nts from Setpoint 5 to Setpoint 8 see par 6 2 5 and following 6 2 4 Quick Clean The QuickClean key allows you to perform a rapid wash of the system or fast recirculation for example by cleaning suctio...

Page 25: ...nother timer and holding down OK for three seconds pastes the whole configuration of the first timer onto this one the operation is then confirmed by pressing OK or cancelled by pressing ESC This spec...

Page 26: ...put for the START STOP control an analog input through which the setpoint to be activated is communicated The analog input can be selected in volgage 0 10 V or in current 4 20mA The setpoint to be act...

Page 27: ...g water For this reason it is generally recommended to empty any pump and hydraulic system during winter when the temperatures are close to freezing point However our system is equipped with the Antif...

Page 28: ...ion works only as long as the system is regularly powered with the electric power disconnected or in the absence of current even accidental such as if the automatic switches have blown due to a storm...

Page 29: ...e19 Internal error e20 e22 Electronic excess temperature e23 Low mains voltage e24 High mains voltage e25 Motor excess temperature e26 Motor blocked e27 Dry operation e28 Pump not primed e29 No curren...

Page 30: ...lue MEMO 1 2 Language English 1 3 Time format 24h AM PM 1 4 Unit of Measure Head Unit m metres ft feet Flow Unit m3 h US GPM Temperature Unit C F 1 5 Pump Limits H max head MAX Q max flow MAX 1 6 Scre...

Page 31: ...ve been restored it will therefore be necessary to reset all the parameters that characterise the system as at the first installation for the sake of convenience the system again proposes the WIZARD p...

Page 32: ...ppliance will be eliminated during the guarantee period contemplated by the law in force in the country where the product is purchased by repair or replacement as we decide The guarantee covers all su...

Page 33: ...668353 Fax 32 2 4669218 DAB PUMPS IBERICA S L Avenida de Castilla nr 1 Local 14 28830 San Fernando De Henares Madrid Spain info spain dwtgroup com Ph 34 91 6569545 Fax 34 91 6569676 DAB PUMPS INC 3226...

Reviews: