ENGLISH
91
Figure 13: Setting the restart pressure
6.5.6
AD: Address configuration
This is only applicable on multi-inverter systems. It sets the communication address to be assigned to the
inverter. The possible values are: automatic (default), or manually assigned address.
The manually assigned addresses can have values from 1 to 8. Configuration of the addresses must be
uniform for all inverters in the series: either all automatic or all manual. Identical addresses are not admitted.
If the address assignment modes are mixed (some manual and some automatic), and also if an address is
duplicated, the relative error is shown. The error is indicated with a flashing “E” in place of the unit address.
If selected assignment is automatic, each time the system is turned on, the addresses are assigned
automatically and may be different from the previous time; this has no effect on correct operation.
6.5.7
PR: Pressure sensor
Setting of the type of pressure sensor used. This parameter enables selection of a ratiometric or current type
pressure sensor. For each type of sensor, different full scales can be selected. When a ratiometric sensor is
selected (default) the input Press 1 must be used for connection. When a 4-20mA current sensor is used, the
relative screw terminals on the input terminal board must be used.
(See Collegamento del sensore di pressione par 2.2.3.1)
Pressure sensor settings
PR value
Type of sensor
Information
Full scale [bar]
0
Ratiometric
501 R 16 bar
16
1
Ratiometric
501 R 25 bar
25
2
Ratiometric
501 R 40 bar
40
3
4-20 mA
4/20 mA 16 bar
16
4
4-20 mA
4/20 mA 25 bar
25
5
4-20 mA
4/20 mA 40 bar
40
Table 16: Pressure sensor settings
NOTE:
The setting of the pressure sensor does not depend on the pressure to be obtained, but on the
sensor to be fitted on the system.
6.5.8
MS: Measurement system
This sets the measurement unit system; either international or Imperial The values displayed are shown in
Table 17.
Units of measurement displayed
Value
International unit of
measurement
Imperial unit of measurement
Restart bar
Temperature °C
°F
Flow
l / min
gal / min
Table 17: Unit of measurement system
Summary of Contents for MCE-22/P
Page 278: ...274 1 276 2 279 3 280 4 282 5 283 6 4 20 284 7 285 8 286 9 287 10 290 11 290 12 292...
Page 279: ...275 IEC 60634...
Page 280: ...276 1 6 MCE 22 P MCE 15 P MCE 11 P 1 1 1...
Page 282: ...278 2 5 2 1 2 1 2 2 1 1 2 1 2 L L L 2 2 4 15...
Page 283: ...279 2 2 2 1 2 2 1 1 3 1 LN 2 2 3 1 3 4 4...
Page 284: ...280 A 3 3 2 2 1 2 4 3 1 UVW 2 2 4 3 50 60 200 1...
Page 286: ...282 4 2 2 3 Press e Flow 5 A B C D d1 d2...
Page 291: ...287 3 9 64 X 128 4 MODE SET 9 7 MODE 1 SET 8 3 EEprom SET 6 SET MODE...
Page 292: ...288 3 1 9 3 2 1 2 3 2 1 MODE SET MODE 8 2 2 5 5 5 2 2 9...
Page 294: ...290 3 2 2 10 SET 10 15 12 11...
Page 296: ...292 12 12 12 GO SB...
Page 297: ...293 4 4 1 Link 8 4 2 4 2 1 Link 2 Link 5...
Page 300: ...296 4 3 1 2 1 4 3 1 3 SET MODE LA RC FN MS FS FL AC AE O1 1 O2 2 4 4 ET 6 6 9 FL...
Page 326: ...322 BL 10 6 24 24 30 LP 180 200 HP OT TE 100 C 85 C OB BT 120 C 100 C OC 10 6 OF 10 6 30...
Page 327: ...323 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 494: ...490 1 492 2 495 3 496 4 498 5 499 6 4 20 mA 500 7 501 8 502 9 503 10 506 11 506 12 508 13 523...
Page 495: ...491 IEC 364 inverter...
Page 496: ...492 1 Inverter inverter inverter 6 inverter MCE 22 P MCE 15 P MCE 11 P 1 1 1...
Page 499: ...495 2 2 2 1 inverter inverter 2 2 1 1 inverter 3 1 LN 2 inverter 2 PVC 3 inverter 1 3 inverter...
Page 502: ...498 4 2 2 3 Press Flow 5 A B C D d1 d2...
Page 507: ...503 3 9 oled 64 X 128 4 MODE SET 9 inverter 7 MODE 1 SET 8 3 EEprom SET 6 SET MODE...
Page 508: ...504 3 1 9 3 2 1 2 3 2 1 MODE SET Setpoint MODE 9 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 9...
Page 512: ...508 12 12 12 GO SB FAULT...
Page 543: ...539 8 8 1 PMW 4 2 8 2 inverter 8 3 8 3 inverter SET EEPROM FLASH setpoint...
Page 599: ...595...