ENGLISH
45
8.2.1
Depth sensor
Tank with security float
Indicate whether you want to use safety floats.
Once you have made your choice, then indicate the polarity of your floats.
No float
(no protection
is set)
High float
(prottection
against
overflow)
Low float
(protection
against empty
tank emergency)
Both floats
(both
protections are
set)
Type of depth sensor
Indicate the type of depth sensor.
Refer to our DAB catalogue for the choice of values.
When first installed, the key is inhibited, as entering a value is mandatory.
Tank height
Set the height of the tank at your disposal, which cannot be higher than the full scale value of the sensor.
The choice of values ranges from a minimum of 0.5 m / 1.6 ft to a maximum of 30 m / 98.4 ft.
Configuration with protection levels
With the depth sensor, it is possible to set a maximum level alarm for "overflow" and a minimum level alarm for "dry run".
If floats for "overflow" and "empty tank emergency" have already been provided, these
inhibit the alarms set with the depth sensor.
The decision to provide both protections is for greater system safety.
Then proceed to set the levels for each pump.
MINIMUM LEVEL ALARM
To be set only if Configuration with protection levels is
selected on the previous page
STOP PUMPS
PUMP 1 LEVEL
PUMP 2 LEVEL
MAXIMUM LEVEL ALARM
To be set only if Configuration with protection levels is
selected on the previous page.