9.10.2 Test SNMP alarm traps
If SNMP alarm traps are configured, the alarm trap functionality can be tested with the button
“Send Test Traps”.
Only the active configured
alarm are forwarded.
This function is found under the DL/PDL configuration menu – SNMP.
9.10.3 Alarm description
Alarm list
Severity
Update
interval
Possible Indication/Failure Cause
Power supply
failure
Degraded
Every 5
minutes this
alarm is
updated.
One power supply in the DL/PDL failed or
one primary power source failed.
RL/VSWR less
than
configured
degraded
threshold
Degraded
Every polling
cycle.
Tx value versus Rx has lowered:
bad physical connections
antenna failure
broken rf- cable
water in the rf-system
splitter failure
Temperature
higher than
configured
degraded
threshold
Degraded
**
Every polling
cycle.
Temperature at the measurement point
has increased above the set degraded
threshold value
PTx signal
less than
0.1W, no Tx
signal
Urgent
Every polling
cycle.
Feeder cable to the sensor broken
Splitter broken
Transmitter broken
check other
sensors