none reverted function (default):
Is the rule activated and the action taken, the action is not reverted if the rule
deactivates again.
Example: Transmission Power is increasing above the set limit an alarm is
triggered, the rules is activated, action is taken
amplifier is switched-off and
remains in this position.
reverted function:
Is the rule activated and the action taken, the action is reverted if the rule
deactivates again.
Example: Transmission Power is increasing above the set limit an alarm is
triggered, the rules is activated, action is taken
amplifier is switched-off after
the rules is deactivated the action is reverted, the amplifier is switched-on again.
reverted with loop function:
Is the rule activated and the action taken, the action is reverted if the rule
deactivates again, after a set time and number of polling cycles where the
activation is repeated, automatically the none reverted mode is set.
Example: Transmission Power is increasing above the set limit an alarm is
triggered, the rules is activated, action is taken
amplifier is switched-off. After
the rules is deactivated the action is reverted, the amplifier is switched-on again
(toggling). After the loop criteria are fulfilled (number of repetitive rule activations)
within the set time period the action is not reverted anymore.