2
WARNING
•
IMPORTANT:
Observe all governing codes and ordinances
during planning and installation. Contact your local building
department for further information.
• To prevent an electric shock hazard, the power supply
must meet the specifications stated below. It is the owner’s
responsibility to make sure that the electrical service meets
electrical requirements and that the electrical outlet has
been properly installed by a licensed electrician.
The appliance installation must be electrically grounded in
accordance with local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/ NFPA 70:
Electrical Requirements
• The range is supplied with a factory installed, 6 foot long, power
cord with a three-prong grounding plug. It is connected to the
chassis at the rear of the range. It must be connected to a
dedicated, grounded three-prong electrical outlet.
• The correct voltage, frequency and amperage must be supplied
to the appliance from a separate, grounded, circuit that is
protected by a properly sized circuit breaker or time delay fuse.
Model
Circuit Required
Total Connected Load*
HGPR36S
120 Vac, 60 Hz, 15 Amp.
120 Vac 60 Hz,
5.0 Amp.
HGPR48S
120 Vac, 60 Hz, 15 Amp.
120 Vac 60 Hz,
8.0 Amp.
*These specifications for reference only. Refer to the rating label for exact specifications
(see below for location).
Planning the Installation
Gas-Supply Requirements
• Installation of this range must conform to local codes or, in their
absence, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
• The range being installed must match the home gas service
(natural or LP gas).
• If using the range above 4000 ft. (1219 m) altitude, ensure it is
equipped for high-altitude use. See the rating label and graphic
on the inside front cover to verify the correct model.
• This table has gas-supply pressure requirements:
GAS-SUPPLY PRESSURE REQUIREMENTS*
Gas Type
Min. Manifold Pressure Minimum Gas-Supply
Pressure**
Natural Gas
5” Water Column
6” Water Column
Liquid Propane (LP)
10” Water Column
11” Water Column
*The gas supply pressure for testing the regulator setting shall be at least 1 inch
water column (249 Pa) above the specified manifold pressure’ **maximum gas supply
pressure for all models: 1/2 psi.
The ratings above are for reference only. See the rating label for exact specifications.
• Use only the factory-installed regulator. The regulator inlet
receives a 3/4” gas line. The range ships with a 1/2”-to-3/4”
adapter connected to the regulator.
B
A
Power
cord
Gas
Inlet
GAS-/ELECTRICAL-ACCESS DIMENSIONS
Model
A
B
HGPR36S
13 1/16” to 14 3/8” (33.2 to 36.5 cm)
7 5/16” (18.6 cm)
HGPR48S
13 1/16” to 14 3/8” (33.2 to 36.5 cm)
4 1/4” (10.8 cm)
Rating
Label