Installation Requirement
s
Gas
Requirements
Provide Adequate Gas Supply
This oven's installation must conform to local codes or, in their absence, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54.
This range's cooktop is designed to operate at a manifold pressure of 5 in. (13 cm) of water column
for natural gas/natural gas at high altitude (NG-H) or 10 in. (25.4 cm) of water column for LP
(propane)/LP at high altitude (LP-H).
Verify that the oven is right for the provided gas service.
When verifying regulator function, inlet pressure must be at least 1 in. (2.5 cm) greater than the
operating (manifold) pressure as given.
GAS SUPPLY PRESSURE REQUIREMENTS*
Gas Type
Minimum Manifold Pressure
Minimum Gas Supply Pressure**
Natural Gas
5” Water Column
6” Water Column
*The gas supply pressure for testing the regulator setting shall be at least 1" water column (249 Pa) above the
specified manifold pressure; **Maximum gas supply pressure for all models: 1/2 psi.
LP (propane) Gas
10” Water Column
11” Water Column
NOTE
•
The pressure regulator at the inlet of the cooktop manifold must stay in the supply line whether
or not natural or LP gas is used.
•
Use only the range's regulator, which must be installed in the gas line that runs from the
cooktop gas inlet to the gas shut-off valve.
•
An external manual shut-off valve must be installed between the gas inlet and range for turning
on/off gas to the appliance.
•
Ensure the connectors are installed by a qualified installer.
•
To avoid leaks and personal injury, never install used connectors on a new product. Use only
new, flexible connectors.
Special
Gas
Requirements
(gas models sold in Massachusetts
)
WARNING
•
Gas leaks may occur in your system, creating a hazardous condition. Such leaks may not be
detected by smell alone; thus, gas suppliers recommend installing a UL-approved gas detector
per manufacturer specifications.
•
The range must be installed by a plumber or gas fitter certified by the State of Massachusetts.
•
A T-handle manual gas valve MUST be installed in the gas-supply line to your range.
•
If using a flexible gas connector, multiple lines must not be connected in series.