background image

5

The blower must also be mounted vertically or at a 

• 

pitch of 2:12 or greater. If the pitch of the mounting sur-

face is less than 2:12, construct a roof curb to mount 

the blower. See 

Installation Preparation

 for exact 

dimensions. 
When mounted in a exposed location shield it to pre-

• 

vent the accumulation of water in the chassis. On 

horizontal installations, point the discharge in the same 

direction as prevailing winds. When mounted vertically, 

the discharge must point down.

Installation Preparation

Prepare the mounting surface and reinforce it if neces-

1. 

sary according to the 

Blower Location and Mounting

 

specifications starting on page 4.
Make a cutout in the center of the mounting location 

2. 

according to Figure 1.
On roofs with a pitch of 2:12 or less, construct a roof 

3. 

curb according to the specifications below. Attach it to 

the mounting surface and seal it around the base.

Installation Planning and Preparation

Blower Location and Mounting (cont.)

Select a location that can properly support or can be 

• 

reinforced to support the weight of the blower (see 

weight table below). The unit requires a mounting sur-

face around the perimeter of the base of the unit 2” 

in width and thick enough to accommodate the 8, 2 

1/2” long mounting screws that are provided with the 

unit. All contact surfaces between the blower and any 

mounting surfaces must be solid and at right angles. 

See Figure 1 for the required mounting surface dimen-

sions.

Model Number

Approximate Shipping Weight

REMP3

35 lbs.

REMP16

55 lbs.

Weight Table 

Dimension

REMP3

REMP16

A

19” (483mm)

26” (660mm)

B

25 1/2” (648mm)

33 1/2” (851mm)

C

4” (102mm)

4” (102mm)

D

2 1/8” (92mm)

2 1/8” (92mm)

E

11” (279mm)

13” (330mm)

F

12 5/8” (321mm)

16 5/8” (422mm)

The base of the remote blower needs to be sealed with 

• 

mastic or the equivalent to prevent leaks.

A

D

2" (51mm)

around entire

perimeter

C

Reinforced

Mounting

Surface

Duct and

Conduit

Cutout

B

F

E

Discharge

Side

Figure 1: 

Required Mounting Surface Dimensions

Figure 2: Installation with Roof Curb (for flat roofs)

Roof Curb

Blower 

Discharge

Prevailing 

Wind

33 1/2" 

(851mm) 

2" 

(51mm) 

26"

(660mm)

30 1/2"

(776mm)

6" 

(152mm) 

2" 

(51mm) 

REMP16 

Roof Curb

25 1/2" 

(648mm) 

2" 

(51mm) 

19"

(483mm)

23 1/4"

(591mm)

6"

(152mm)

2" 

(51mm) 

REMP3 

Roof Curb

Figure 3

Summary of Contents for REMP16

Page 1: ...265 Rev G Suitable for use in a household cooking area Suitable for use with solid state controls To complete this blower a Dacor hood assembly or Dacor raised vent must be purchased separately See the hood or raised vent installation instructions to determine suitability ...

Page 2: ...completely and care fully before you begin the installation process Leave these installation instructions with the customer Customer Keep these installation instructions for future reference and the local electrical inspector s use 2008 Dacor all rights reserved If You Need Help If you have questions or problems with installation contact your Dacor dealer or the Dacor Customer Service Team For rep...

Page 3: ...SONS OBSERVE THE FOLLOWING Use this unit only in the manner intended by the a manufacturer If you have questions contact the manufacturer Before servicing or cleaning unit switch power off b at service panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warn ing device ...

Page 4: ... the location of the fuse or circuit breaker panel so that the cus tomer knows where and how to turn the power off warning General Safety Precautions To reduce the risk of fire electric shock serious injury or death when using this blower follow basic safety precautions including the following A minimum of two people are required to safely install this appliance Never allow the filters or vent ope...

Page 5: ...t Hole C L C L C L C L 26 660mm 32 1 4 819mm 3 5 8 92mm 12 1 4 311mm Mounting Flange 33 1 2 851mm 9 1 2 241mm 13 1 8 333mm Discharge Intake Collar Power Supply Conduit Location C L C L C L C L 24 1 4 616mm 9 9 16 243mm 10 Nom 254mm 11 1 2 292mm Discharge Intake Collar 5 13 16 148mm 8 Nom 203mm 7 15 16 202mm Discharge Intake Collar All tolerances 1 16 0 1 6 mm 0 unless otherwise noted REMP3 REMP16 ...

Page 6: ...ted on each end by a 1 2 UL certi fied strain relief The power is turned on and off by the power switch on the approved ventilation device The correct voltage frequency and amperage must be supplied to the hood or raised vent and the blower from a grounded single phase circuit that is protected by a properly sized circuit breaker or time delay fuse The circuit must have the capacity to supply the ...

Page 7: ... support or can be reinforced to support the weight of the blower see weight table below The unit requires a mounting sur face around the perimeter of the base of the unit 2 in width and thick enough to accommodate the 8 2 1 2 long mounting screws that are provided with the unit All contact surfaces between the blower and any mounting surfaces must be solid and at right angles See Figure 1 for the...

Page 8: ...n page 5 and meet local codes and ordi nances Consult the hood or raised vent installation instructions for additional part requirements Installation Before installing the blower unpack the unit and check 1 for physical damage to the motor and blower assembly To do so reach in through the intake collar and spin the fan blades slowly They should spin freely and qui etly without vibration Installati...

Page 9: ...e GND blower 13 power terminal see Figure 9 Tighten the terminal screw firmly into place Check the wires from the blower wiring harness to 14 make sure that they are firmly attached to the terminal according to Figure 9 Reconnect any wires that are loose Make sure all terminal screws are tight Replace the blower s top cover and screws 15 Secure the other end of the wiring conduit to the hood 16 or...

Page 10: ...EMP16 1000 CFM 994 8 CFM Airflow CFM Cubic feet minute Static pressure inches of water 0 1 0 2 0 3 0 4 0 5 0 100 200 300 400 500 600 700 REMP3 Blower Performance Airflow CFM Cubic feet minute Static pressure inches of water 0 0 5 1 0 1 5 2 0 2 5 200 400 600 800 1000 REMP16 Blower Performance At 0 static pressure ...