9.3 Dielectric Fluid Sampling
Dielectricfluid samples should be taken at least on an annual basis and analyzed by DGA (Dissolved Gas
Analysis). RoutineDGAtestingisoneofthebestmethodsofdeterminingthe“Health”ofatransformer.
Althoughtheultimatefailureofatransformermaybeimpossibletopredict,routineoiltestingcanoften
indicate a detrimental internal condition before it destroys the unit.