25
Auto Mode
(1) In Auto Mode
After the indoor fan is operated for 20 seconds in the Auto Mode the unit will operate automatically by selecting
operating Mode according to the room temperature
(2) Selecting Operating Mode Again
Room temperature meets desired temperature and the compressor stops running over 30 minutes, then the unit
selects operating Mode again.
3 min. Time Delay of Compressor
In normal operation, there is a time delay of three minutes between turn off and turning back on including initial
power up.
ROOM TEMPERATURE
DT-2°C RT
DT-2°C
≤
RT
≤
DT+3°C
DT+3°C RT
OPERATING MODE
Heating
Dehumidifier
Cooling
FLAP POSITION
Heating Position
Cooling Position
Cooling Position
(RT: Room temperature)
>
<