When Module exposed to sunshine or other lights, it can produce DC, in this case it may cause electric shock hazard 

if touch electrical parts.

Focus sunlight on to PV module via mirror or lenses is prohibited.

Temples glass and backsheet have protective effect, broken PV modules have electrical risks(electric shock and 

burnt), this kind of modules can not be fixed or repaired, should be replaced in time.

Under nominal outdoor condition, the current and voltage produced by module are different with datasheet. The 

parameters in datasheet is tested under STC condition, therefore when determining other components rated voltage, 
wire capacity, fuse rate, controller capacity and PV module power output relative datas of PV system, please refer to 
the short circuit current and open circuit voltage of the PV module, and design and install the system in 125% of the 
value as well.

In case to lower electric shock or burnt risk, it’s better to cover the PV modules by opaque material when installing.  

PV array installation job should be operated under isolating sunlight condition, installation and maintenance also 

should be handled by professionals. 

If batteries bank equipped in the PV system, it should comply with battery supplier’s suggestion.

PV modules shall not replace rooftop and wall material, partial replacement is also not allowed.

Don’t install PV modules in the area where may has combustible gases.

Touch PV module’s electrical part by hand directly is prohibited, should use insulating tools to handle the electrical 

connecting.

Don’t dismantle any components of DAH Solar PV module personally.

Don’t lift modules by junction box or connecting cables.

All the modules system should be connected to ground, if without special stipulations, please refer to International 

Electrical Standard or other International Standards.

Please do not stand, sit, lying on modules, it may damage modules and also have injured risks. 

Same size and specification models modules can only be connected together.

During delivery please make sure transport tools or modules are not subjected to large vibrations, vibrations may 

cause modules damage or cells microcrack inside of modules.

During all the delivery,don not allow modules to fall onto ground from transport tools, house or hand, this will 

damage modules or cells inside.

 

Don’t wipe the module with corrosive chemicals.

When loads are working, please do not disconnect the modules.

WARNING

The maximum permitted

system voltage (DC) of the modules is

1000V DC(Option 1500V DC)

PV module

application class is A

* Electrical performance parameter of module, such as nominal value of Isc

Voc and Pmas has ±3% random error 

compared with value of STC. The standard testing environment of module is: Irradiance 1000/m

2

Cell temperature 

25

℃、

Spectrum AM 1.5.

* Normally, the current and voltage of module, will be a little higher compared with the value under STC, so when 

confirmed the associated parameters of solar system accessories, such as rated voltage

cable capacity

fuse 

capacity and module power, the corresponding short circuit current and open circuit voltage should be amplified by 

1.25 times.

* The maximum number of modules per series string must be calculated according to the requirements. The value of 

the Voc in the local expected minimum temperature cannot exceed the maximum system voltage value specified of 

the module (According to IEC61730 safety test, the maximum system voltage of DAH Solar Module is DC1000V) and 
other DC electrical components require values.

* The Voc correction factor can be calculated according to the following formula: CVoc=1-

β

Voc×(25-T), T is the 

minimum ambient temperature expected for the installation of the system, 

β 

(% / 

) is The temperature coefficient of 

the selected module Voc (according to the corresponding module data sheet).

* If the reverse current which probably exceed the maximum fuses current of module passed through the module, the 
modules must be protected by an equivalent current protection device. If the number of parallel is more than or equal 
to 2 strings, there must be equipped an overcurrent protection device on each series of modules.

ELECTRICAL INSTALLATION

SERIES

CONNECTION

PARALLEL

AFTER

SERIES

Connector

Summary of Contents for DHM-72X10/FS

Page 1: ...user MANUAL Reinvents the PV Module ...

Page 2: ...er During delivery please make sure transport tools or modules are not subjected to large vibrations vibrations may cause modules damage or cells microcrack inside of modules During all the delivery don not allow modules to fall onto ground from transport tools house or hand this will damage modules or cells inside Don t wipe the module with corrosive chemicals When loads are working please do not...

Page 3: ...n Hemisphere Summer Winter PV module Spring Autumn Southern Hemisphere Climatic Condition 40 C 85 C 4 F 185 F Ambient temperature Don t install PV modules in a flooded risk area Don t install in raining snowing or windy weather conditions Please wear protective headcoats insulated gloves and rubber insulated shoes during installation job To avoid unnecessary touching of the PV module during instal...

Page 4: ...flat washer spring washer and nut as shown in Figure 1 and tighten to a torque of 16 20 N m 140 180lbf in All parts in contact with the frame should use flat stainless steel washers of minimum 1 8mm thickness with an outer diameter of 20 24mm 0 79 0 94in The frame of each module has 4 φ9 14mm mounting holes ideally placed to optimize the load handling capability to secure the modules to supporting s...

Page 5: ...se of the products whether express or implied DAH Solar reserves the right to modify the manual PV products specifications or product information The modification of any information may be due to business requirements technical level or other objective environment but it does not represent the negation of the original information Information of this manual is reliable knowledge and experience of DAH...