16
No.
Port
Description
8
K2, GND
Signal port for opening the turnstile on exit. It can receive the open
turnstile signal from the control board or the face recognition module.
K1, GND
Signal port for opening the turnstile on entry. It can receive the open
turnstile signal from the control board or the face recognition module.
XF, GND
Fire alarm signal input port. When a signal is received, the turnstile arm
automatically falls down. To power on the turnstile, you need to
manually push the arm down, and then lift it up to a level position.
9
TMP1, GND
Reserved port.
12 V, GND
Provides operating voltage for the fan.
10
TX2, GND, RX2
RS-232.
Control Board Cable Connection
5.2
For 2 IC card readers, set the DIP switch on the access control panel to 00000000 (default).
Set the DIP switch on the face recognition module panel to 00000001.
The default IP of the access control is 192.168.1.108. The default username and password are
admin and admin123 respectively.