Local Configurations
92
Alarm setting
Figure 4-77
Select the event type.
Step 2
Local Alarm: The alarm signal detected by the alarm input port on the Device.
IPC Disconnect: The alarm signal is generated when the IP camera is
disconnected.
In the
Alarm In
list, select a channel number, and then select the
Enable
check box.
Step 3
If
Local Alarm
is selected, select a channel from Channel 1 to Channel 7.
If
IPC Camera Offline
is selected, select a channel from Channel 9 to Channel 12.
Configure the parameters. For details, see Table 4-33.
Step 4
Table 4-33 Alarm parameters description
Parameter Description
Type
If
Local Alarm
is selected, configure this parameter.
Normal Open: The alarm signal is disconnected normally. The alarm is
activated when alarm signal is closed.
Normal Close: The alarm signal is closed normally. The alarm is canceled
when alarm signal is disconnected.
Trigger
If
Local Alarm
is selected, configure this parameter.
High: The alarm signal is 12V/24V voltage. Low: The alarm signal is signal
ground.
Alarm
Name
If
Local Alarm
is selected, configure this parameter.
In the
Alarm name
box, enter a name for the alarm.
Overlay
If
Local Alarm
is selected, configure this parameter.
Select the
Overlay
check box to display the alarm information on the channel
window.
Anti-dither
If
Local Alarm
is selected, configure this parameter.
Configure the event detection lasting time. The system records only one event
during this period. The value ranges from 1 second through 600 seconds.