SFLC-212-173
46
(2) 221A to 227A Analog output setting 【With option】
Various setting of analog output is performed.
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
221A
Ao1 output
factor
RESET/
SHIFT
MAX/MIN
222A
Ao2 output
factor
RESET/
SHIFT
MAX/MIN
223A
Ao3 output
factor
RESET/
SHIFT
MAX/MIN
224A
Current output
intrinsic
sensitivity
227A
Low input cut
226A
Reactive power
output intrinsic
sensitivity
225A
Active power
output intrinsic
sensitivity
RESET/
SHIFT
MAX/MIN
RESET/SHIFT
MAX/MIN
◆ 221A to 223A AO (analog output) 1 to 3 output factor.
Sets the output factor of each analog outputs.
Selection by + and - , set value is updated by SET .
Default setting:
AO1 A(V) (3φ3W),A(U) (1φ3W U-W-N),A (1φ2W)
AO2 V(UV)(3φ3W),V(UN)(1φ3W U-W-N),V (1φ2W)
AO3 W (3φ3W / 1φ3W / 1φ2W)
+
-
-
+
9:DA(W)
-
+
8:DA(V)
-
+
7:DA(U)
-
+
6:A(W)
5:A(V)
+
-
4:A(U)
+
-
3:V(WU)
+
-
2:V(VW)
+
-
1:V(UV)
OFF:
Nothing
-
+
-
+
-
+
-
+
-
+
15:MDW
+
-
14:DW
+
-
13:W
+
-
12:MDA(W)
+
-
11:MDA(V)
10:MDA(U)
+
-
18:Hz
17:cosφ
16:var
At 3φ3W
◆ 224A Current output intrinsic sensitivity,
225A Active power output intrinsic sensitivity,
226A Reactive power output intrinsic sensitivity.
Output intrinsic sensitivity (% of rated input power value to
an output upper limit value) is set about each analog output of
current, active power, and reactive power.
The setting range can be selected from the following.
Current :40.0 to 120.0% (0.1% step)
Active power :30.0 to 120.0% (0.1% step)
Reactive power:30.0 to 120.0% (0.1% step)
Selection by + and - , set value is updated by SET .
Default setting:100.0%(Current, Active power),50.0%(Reactive power)
Example) 3φ3W, 9000V, 100.0A, 1200kW range, Analog output DC4 to 20mA
・Set 100.0%. Analog output is DC20mA in 1200kW of primary inputs.
・Set 80.0%. Analog output is DC20mA in 1200kW×0.8=960kW of primary input.
◆ 227A Low input cut
It is the function which makes analog output a lower
limit at the case of a minute input (input which
corresponds to 0.5% or less).
A function can be selected from ON (Use) and OFF
(Non-use).
Selection by + and - , set value is updated
by SET .
Default setting:OFF (Non-use)
Power-output intrinsic
sensitivity,
Setting No.
New setting
Current setting
Ao1 output factor
Setting No.
New setting
Current setting
Low input cut
New setting
Current setting
Setting No.
Setting factor