Setting item
3-phase 3-wire
Single-phase
3-wire
(U-N-W)
Single-phase
110V input
220V input
110V input
220V input
10
Measurement
display
ON/OFF
Voltage
ON
ON
ON
Current
ON
ON
ON
Demand current
ON
ON
ON
Active power
ON
ON
ON
Demand power
ON
ON
ON
Reactive power
ON
ON
ON
Power-factor
ON
ON
ON
Frequency
ON
ON
ON
Watt-hour of power receiving ON
ON
ON
Watt-hour of power
transmission
ON
ON
ON
var-hour of power receiving
ON
ON
ON
var-hour of power
transmission
ON
ON
ON
11
Input
circuit
Phase line change (
6
)
3φ3W
1φ3W (U-N-W)
1φ2W
Input voltage (
7
)
110V
220V
150V
110V
220V
12 Measurement Tidal current measurement
General measurement
General
measurement
General measurement
13
Analog
output
adjustment
(
5
)
Output 1
Bias adjustment
0.0%
0.0%
0.0%
Span adjustment
100.0%
100.0%
100.0%
Output 2
Bias adjustment
0.0%
0.0%
0.0%
Span adjustment
100.0%
100.0%
100.0%
Output 3
Bias adjustment
0.0%
0.0%
0.0%
Span adjustment
100.0%
100.0%
100.0%
Note(
1
) A setting item is not displayed in case there is no corresponding option.
Note(
2
) When the input circuit phase line switching setting is changed, the setting values of setting 1 and
setting 2 (No. 1 to 10 in the table) return to the default setting values of the switched phase line.
However, the value of setting 3 (No. 11 to 13 in the table) does not return to the initial setting.
Note(
3
) When phase line change setting of an input circuit is set as 3φ3W (or 1φ2W) and the input voltage
setting is changed, the voltage range returns to the default value of the phase line.
(For example:In case of 3φ3W, 6600V at the case of 110V setting, 220.0V at the case of 220V setting.)