(1) 311 to 312 Input circuit setting
Sets the input circuit and phase wire and input voltage / phase-voltage full scale.
311
Input circuit phase
wire change
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
312
Input voltage
◆ 311 Input circuit phase wire change
Sets the input circuit and phase wire (1φ3W).
Selection by + and - , set value is updated by pushing SET
3 seconds or more.
Default setting:3φ3W (No designation)
<Caution>
・When this setting is changed, it will become the default setting
of the input circuit after all set values changing.
・The right measurement cannot be performed if setting of actual
connection and phase wire are different.
◆ 312 Input voltage
Set the input voltage (3φ3W, 1φ2W) or phase-voltage full scale (1φ3W).
In 3φ3W/1φ2W and 1φ3W, the contents of a setting are different.
Selection by + and - , set value is updated by SET .
Default setting:150V (1φ3W)
Default setting:110V (3φ3W,1φ2W or no designation)
・3φ3W,1φ2W ・1φ3W
Setting of 300V, Output is AC0 to 150V/DC4 to 12mA.
Setting of 150V, Output is AC0 to 150V/DC4 to 20mA.
Input circuit and
phase wire change
Current setting
Input-voltage rating (3φ3W)
Phase-voltage full scale (1φ3W)
UN WN alternate display
(Phase display U-N-W)
110V
+
-
220V
-
+
150V
+
-
300V
-
+
Setting No.
New setting
Current setting
Setting No.
New setting
Current setting
Setting No. New setting
3φ3W
+
-
1φ3W
(U-N-W)
-
+
1φ3W
(U-N-V)
+
-
+
-
1φ3W
(V-N-W)
+
-
1φ2W