SMLC-213-154 

 

 
 
 
 
 
 
 

INSTRUCTION MANUAL 

 

MAXIMUM (MINIMUM) SUPER MULTI-METER 

 

SMLC-110L 

 

Hardware Model D 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 

Summary of Contents for SMLC-110L

Page 1: ...SMLC 213 154 INSTRUCTION MANUAL MAXIMUM MINIMUM SUPER MULTI METER SMLC 110L Hardware Model D...

Page 2: ...product must be set before use Please set correctly after reading this instruction manual About dew condensation If the temperature and humidity of an installation change rapidly when a product is a...

Page 3: ...ns change etc please contact us Setting This unit requires setting and confirmation of the measuring range etc before use Wrong setting if any causes malfunction of the unit If setting should be wrong...

Page 4: ...n 1 to 5V 1 to 5V 13 Analog output adjustment Output 1 Bias adjustment 0 0 0 0 Span adjustment 100 0 100 0 Output 2 Bias adjustment 0 0 0 0 Span adjustment 100 0 100 0 Output 3 Bias adjustment 0 0 0 0...

Page 5: ...etting display 14 4 3 Operation 15 4 3 1 The main monitor display element change 15 4 3 2 Phase line display change 15 4 3 3 Ground fault phase detection display change 16 4 3 4 Setting value check 16...

Page 6: ...2 circuit can be taken out Option And an output factor can be selected by setting Two external operation inputs are possible Option And selection of reset input and a display change input is possible...

Page 7: ...set point This switch resets various alarms And in the maximum and the minimum measurement display it is used as a switch that resets the maximum and the minimum value In setting mode it is used as a...

Page 8: ...angle since the contrast changes according to the monitoring angle 1 For upper case installation 2 For lower case installation 3 Wide viewing angle model 60 Side view 10 60 60 Top view Side view Side...

Page 9: ...roblem on characteristics Caution on connection 1 Mount the terminal cover without fail for safety after the end of connections 2 Separate the input wiring and output wiring from each other without fa...

Page 10: ...In setting mode it is used for change of a set point DISPLAY A phase between lines display of current voltage is changed It is used in case it terminates setting mode And it is used in case it return...

Page 11: ...nge No operation 10 minute No operation 10 minute Phase line display change Set point check No operation 10 minute DISPLAY or Push 3 seconds SET Setting mode 1 No operation 10 minute DISPLAY or Settin...

Page 12: ...value and the minimum value about the measurement factor which performs holding of the maximum value and the minimum value by switch operation These maximum values and the minimum value are reset by...

Page 13: ...etection by OFF backlight turn on the lights at the same time a screen is changed After that in case it does not operate it for 5 minutes backlight goes out Please refer to 4 3 3 Ground fault phase de...

Page 14: ...ting by measurement at the main monitor or the sub monitor a measurement value constitutes a blinking display The displays after an alarm return In case a return method is automatic reset setting It r...

Page 15: ...in this setting mode Setting mode 1 No 111 Display pattern Setting mode 2 Setting of measurement range analog output and measurement display ON OFF is mainly performed And initialization of a setting...

Page 16: ...zero phase voltage Zero phase voltage Default display 4 3 2 Phase line display change A phase line display of voltage is changed Everything which is being indicated A change is performed by DISPLAY Th...

Page 17: ...tion all the minimum values of RN SN TN will be 0V In that case please check a ground fault phase at the maximum value of RN SN TN phase voltage 4 3 4 Setting value check A voltage range VT ratio and...

Page 18: ...T and RESET SHIFT together for longer than 3 seconds Setting mode 3 Press SET and DISPLAY together for longer than 3 seconds Reference This operation can perform the maximum the minimum display and a...

Page 19: ...FT for longer than 1 seconds Caution An alarm output will be reset if this operation is performed by instant measurement display Please be sure to perform this operation after displaying the maximum v...

Page 20: ...on setting can perform same operation in external operation input Please refer to 5 3 2 Setting mode 2 3 external operation input setting for the setting method Please refer to 6 3 Option for the exte...

Page 21: ...est Output test of alarm 1 is performed 28 124AL Alarm 2 factor Set the output factor of alarm 2 OFF 28 125AL Alarm 2 return method Set the output action at the case of reset of alarm 2 Automatic rese...

Page 22: ...251 Initialization of setting value All set values are initialized Return to initial set value 35 Setting mode 3 Function table Set No Function Functional description Default setting Important setting...

Page 23: ...DISPLAY Returns to display mode 33 Setting of output factor in analog output 2 AO2 222A Press SET and RESET SHIFT together for longer than 3 seconds Press MODE 211 221A Press RESET SHIFT Select an out...

Page 24: ...ing of display factor in main monitor 112 Press SET for longer than 3 seconds Press RESET SHIFT 111 112 Select an display factor by and Press SET Selected display factor is entered Press DISPLAY Retur...

Page 25: ...3 seconds Press MODE Press RESET SHIFT 111 121AL 122AL Select a return method by and Press SET Selected return method is entered Press DISPLAY Returns to display mode 28 Setting of return method in a...

Page 26: ...ET Selected function is entered Press DISPLAY Returns to display mode 30 8 Backlight setting Each parenthesized number shows a setting number and this number is displayed on the setting screen Items S...

Page 27: ...o V RS Hz V RS Displays set factor 14 Displays factor Measurement factor Main monitor Voltage VRS VST VTR VRN VSN VTN Maximum zero phase voltage MVo Zero phase voltage Vo Frequency Hz Sub monitor Left...

Page 28: ...r Set values are updated by SET Setting Under bar Setting New setting Current setting Manual setting value 0 Pattern 1 Pattern 2 Pattern 3 Pattern 6 Pattern 7 V RS 4 V ST 5 Default setting V TR 6 Hz 7...

Page 29: ...ase of a reset of alarms 1 and 2 can be selected from AUTO automatic reset and HOLD manual reset In AUTO automatic reset an alarm output also constitutes OFF according to a reset of an alarm In HOLD m...

Page 30: ...er limit alarm value and lower limit alarm value of 3 phase voltage line voltage are setting Setting range 30 to 150 1 step and OFF Non use Selection by and set value is updated by SET Default setting...

Page 31: ...setting 0 1 seconds 143 Ground fault phase detection display automatic change Set the whether it changes from a measurement display an instantaneous measurement display the maximum and the minimum mea...

Page 32: ...etting 3 Middle 5 3 2 Setting mode 2 Setting mode 2 is selected by pressing SET and RESET SHIFT switches continuously for longer than 3 seconds Pushing MODE switch performs movement of setting item Th...

Page 33: ...play OFF 1 3 display ON 213 Frequency range Frequency measurement range can be selected from 45 0 to 55 0Hz 55 0 to 65 0Hz 45 0 to 65 0Hz Change of this setting also sets the analog output range of a...

Page 34: ...s only phase voltage input product Default setting AO1 MVo AO2 V RS AO3 V ST AO4 V TR OFF Nothing 1 MVo 2 Vo 3 V RN 4 V SN 5 V TN 6 V RS 7 V ST 8 V TR 9 Hz 225A Low input cut This function which makes...

Page 35: ...ET Alarm reset MAX MIN RESET Maximum minimum reset R S T DISP Phase change Measurement factor DISP Measurement factor change About the setting display in an external operation input function Function...

Page 36: ...tage 243 Zero phase voltage 244 Frequency RESET SHIFT RESET SHIFT RESET SHIFT 5 251 Initialization of setting value Each set value is initialized returns to default setting 251 Initialization of setti...

Page 37: ...t the about a zero phase input voltage Selection by and set value is updated by SET Default setting 190V Caution If an actual input and an actual setup differ from each other it becomes impossible to...

Page 38: ...T SHIFT RESET SHIFT 342 Ao1 SPAN adjustment 343 Ao2 BIAS adjustment 344 Ao2 SPAN adjustment 347 Ao4 BIAS adjustment 346 Ao3 SPAN adjustment 345 Ao3 BIAS adjustment RESET SHIFT RESET SHIFT RESET SHIFT...

Page 39: ...aximum zero phase voltage Ground fault phase detection 0 05 seconds 0 1 seconds 0 15 seconds 0 2 seconds 0 5 seconds 1 second 2 seconds 3 seconds 5 seconds 90 response Time interval setting Voltage 0...

Page 40: ...supply 1 AC85 to 264V 50 60Hz 10VA Rated voltage AC100 110V 200 220V DC80 to 143V 6W Rated voltage DC100 110V for both AC and DC uses 2 DC20 to 56V 6W Rated voltage DC24 48V Rush current Time constan...

Page 41: ...ess Protection code IP40 Material Case Cover ABS V 0 Terminal block PBT Terminal cover Polycarbonate Color Black Munsell N1 5 Mass Approx 600g Blackout guarantee Maximum value Minimum value Ground fau...

Page 42: ...rm display and alarm output Detects by the minimum phase Setting accuracy 1 0 to the value which set a full scale to 150 Setting range 30 to 150 1 step or OFF not use Full scale 150 External operation...

Page 43: ...n method is a manual reset Please check a setting 7 2 Test In case this product is tested a special setting or operation is not needed fundamentally However the following test should operate it along...

Page 44: ...1 13 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774 54 13...