SFLC-211-185
45
◆ 213 Current range
Sets the current range (primary current). Change of this setting also sets the measurement range of
active power and reactive power automatically simultaneously.
Selection by + and - , set value is updated by SET .
Default setting:100.0A (3φ3W), 500.0A (1φ3W), 50.00A (1φ2W)
Current-measurement range
◆ 214 Current display intrinsic sensitivity
Sets the full scale of current meter.
The setting range is 40 to 120% of CT ratio. And, it can select from the following values.
Selection by + and - , set value is updated by SET .
Default setting:100.0A (3φ3W), 500A (1φ3W), 50.0A (1φ2W)
The measurement range (current, active
power, reactive power) which can be
set. (×10
n
)
Example)
In case of CT ratio=100.0A.
・40% of 100A is 40A.
・120% of 100A is 120A.
A measurement range can be
selected within the limits
of 40 to 120A.
Therefore, a left table
A measurement range can be
selected from
40/42/45/48/50/56/60/64/72/
75/80/84/90/96/100/120A.
1.□ 1.0/1.2/1.4/1.5/1.6/1.8
2.□ 2.0/2.4/2.5/2.8
3.□ 3.0/3.2/3.6
4.□ 4.0/4.2/4.5/4.8
5.□ 5.0/5.6
6.□ 6.0/6.4
7.□ 7.2/7.5
8.□ 8.0/8.4
9.□ 9.0/9.6
◆ 215 Digit number of current range
Sets the digit number of current range.
Selection by + and - , set value is updated by SET .
Default setting:4 digits
The unit may be changed if the number of digits is changed.
Example) 1000A 1.00kA
Current display intrinsic
sensitivity
Setting factor
Setting No.
New setting
Now setting
750A
800A
900A
1000A
1200A
1500A
1600A
1800A
2000A
2500A
3000A
4000A
5A
6A
7.5A
8A
10A
12A
15A
20A
25A
30A
40A
50A
5000A
6000A
7500A
8000A
9000A
10kA
12kA
15kA
20kA
30kA
60A
75A
80A
100A
120A
150A
200A
250A
300A
400A
500A
600A
4 digits
3 digits
+
-
-
+
Setting No.
Now setting
Digit number of current range
Setting factor
New setting