SFLC-211-185
49
(3) 231P~232P Pulse output setting 【With option】
Various setting of a pulse output is performed.
231P
Pulse output factor
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
232P
Pulse unit
◆ 231P Pulse output factor,
Sets the output factor of pulse output.
Selection by + and - , set value is updated by SET .
Default setting:Wh
OFF:
Nothing
1:Wh
+
-
+
-
2:-Wh
+
-
3:varh
(LAG)
+
-
6:-varh
(LEAD)
-
+
5:-varh
(LAG)
-
+
4:varh
(LEAD)
-
+
◆ 232P Unit of pulse output
Sets the pulse unit of pulse output.
A pulse unit can be selected from four types.
The pulse unit that can be selected is decided with
full-load power.
Default setting:10kWh/pulse [3φ3W, 110V input]
1kWh/pulse [1φ3W/1φ2W, 110V input]
0.1kWh/pulse [3φ3W/1φ2W, 220V input]
(4) 241 External operation input setting【With option】
Various setting of external operation input is performed.
◆ 241 External operation input function
The function of each external operation
input (alarm reset, maximum / minimum reset,
all reset) can be selected.
Selection by + and - , set value is
updated by SET .
Default setting (With alarm-output option)
Alarm reset
Alarm reset
+
-
+
-
-
+
Maximum /
minimum reset
All reset
(Alarm,Maximum/minimum)
・About the setting display in an external operation input function
Function
The contents of a display at the function setting
"Now setting"
display point
"New setting"
display point
Alarm reset
"ALARM" and "RESET" are displayed by turns by 7 segment
display.
Sub monitor
(right)
Main monitor
Maximum /
minimum reset
Flashing of RESET, by 7 segment display.
And, maximum and minimum of guidance displayed by turns.
All reset
"ALL" and "RESET" are displayed by turns by 7 segment
display.
Pulse output factor
New setting
Setting No.
Now setting
Pulse unit
New setting
Now setting
Setting No.
Setting factor New setting
Setting No.
ALARM and RESET are
displayed by turns.
(Alarm reset)
Maximum and minimum
are displayed by
turns.
Flashing of RESET.
(Maximum / minimum
reset)
Now setting