SFLC-211-185
62
(2) Alarm output check 【 With an option 】
Even if this product does not have input, it can perform ON/OFF test of an alarm output (relay-contact output).
Whenever it pushes SET , ON and OFF change.
Default:OFF
Output OFF Output ON
Alarm test
(3) Analog output check 【With an option】
Even if this product does not have input, it can test analog output (three circuits).
Ao1 check
RESET/
SHIFT
MAX/MIN
RESET/
SHIFT
MAX/MIN
Ao2 check
Ao3 check
RESET/
SHIFT
MAX/MIN
◆ AO (analog output) 1 to 3 check.
Sets the output factor about each analog output.
It selects 0%(4mA), 50%(12mA), and 100%(20mA)
with + or - switch. If SET is pushed,
analog output will output.
Default:0% (4mA)
(4) Pulse output check 【With an option】
Even if this product does not have input, it can test pulse output.
A push on SET outputs the pulse of a rated power. Pulse unit are the settings of "232P Pulse unit".
Default:OFF
SET
The status of lights
at the output time.
The status of
lights at the
output time.
Analog output
factor
Output value
SET
The status of lights
at the output time.