Protocol Point Summary - BACnet
The following section defines the parameters for all BACnet objects available from the unit controller
to the network (see Table 4 below). The shaded data points with numbers are the data points listed in
Table 3.
Table 4. Comprehensive List of BACnet Objects
Network Control Property
Page
Read,
Writ
e
1
Obje
ct
Type
Insta
n
ce
Description
Application Version
R Device
* Application version software running in the chiller.
Chiller Location
34 W Device
* Defines where the chiller is physically located. By
default, this is blank.
Chiller Model
R Device
* This defines the model of the chiller.
Active Setpoint
R
AV
5 15.08 to 149.9°F (-9.4 to 65.5°C)
*Actual Capacity
28 R AV 2
0–100%
*Active Capacity Limit (Output)
30 R AV 1
0–100%
*Capacity Limit Setpoint - Network
W
AV
3 0 to 100%; Default=100%
*Chiller Enable Output
R
BI
7 0=Disable, 1=Enable
*Chiller Enable Setpoint
W
BV
2 0=Disable, 1=Enable
Chiller Capacity Limited
32 R BI 6
0=Not
Limited,
1=Limited
Chiller Local/Network
34 R BI 3
0=Network,
1=Local
Chiller Mode Output
R
MSV
2 1=Ice, 2=Cool, 3=Heat
Chiller Mode Setpoint – Network
36 W MSV 3 1=Ice, 2=Cool, 3=Heat
, Default=Cool
Chiller On Off
R
BI
4 0=Chiller Off, 1=Chiller On
*Chiller Status BACnet
37 R MSV 1
1=Off, 2=Start, 3=Run, 4=Preshutdown,
5=Service
Compressor Average Current
R
AI
9 0–2000 amps (less for some models)
Compressor Discharge Refrigerant Pressure
40 R AI 81
0 to 410.0217 PSI
Compressor Discharge Refrigerant
Temperature
R
AI
63 -40°F to 257°F (-40°C to 125°C)
Compressor Discharge Saturated Refrigerant
Temperature
R
AV
26 -15 to 185°F (-26.2 to 85°C)
Compressor Percent RLA
R
AV
8 0% - 150% RLA
Compressor Power
R
AI
45 0 –600 kW
Compressor Run Hours
42 R AV 74
0
–999,999
Compressor Starts
43 R AV 92
0
–65,535
Compressor Suction Refrigerant Temperature
44 R AI 105 -40°F to 257°F (-40°C to 125°C)
Compressor Average Voltage
40 R AI 27
0–10,000
volts
*Condenser Entering Water Temperature
R
AI
3 -40 to 257°F (-40 to 125°C)
Condenser Flow Switch Status
R
BI
1 0=No Flow, 1=Flow
*Condenser Leaving Water Temperature
R
AI
4 -40 to 257°F (-40 to 125°C)
Condenser Pump #1 Run Hours
46 R AV 110 0
–999,999
Condenser Pump #2 Run Hours
46 R AV 111 0
–999,999
Condenser Refrigerant Pressure
R
AI
99 0 to 410.0217 PSI (-140 to 2827 kPA)
Condenser Saturated Refrigerant Temperature 47
R
AV
44 -15.16 to 185°F (-26.2 to 85°C)
Compressor Suction Refrigerant Pressure
44 R AI 123 0-131.9988
psi
Compressor Suction Saturated Refrigerant
Temperature
R
AV
50 -15.16 to 104°F (-26.2 to 40°C)
Condenser Water Flow Rate
47 R AI 147 0 to 10,001.55 GPM (0 to 631 L/s)
Condenser Pump #1 Status
R
BI
11 0=Pump Off Request, 1=Pump On Request
Condenser Pump #2 Status
R
BI
12 0=Pump Off Request, 1=Pump On Request