30
ED 15117
capacity long
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT
Index
SNVT Size
SCPT_Reference
SCPT
Index
nciCapacityLim
(configuration)
Chiller SNVT_lev_percent
81
two
bytes SCPTlimitChlrCap
81
Active Capacity Limit Output
This read only network variable is a measure of the ratio of operating capacity limit to full capacity
expressed in percent. This value is the lowest of all limits specified by the operator, analog Demand
Limit input, or Network Capacity Limit Setpoint.
Measurement
Units
Data Type
Usable Range
Default Value
Percent of maximum
capacity
% BACnet:
Real
L
ON
W
ORKS
: Fixed-Point Scalar
signed long
0% to 100%. NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
2
1
Present Value
85
Object Name
ActiveCapacityLimit
LonWorks
L
ON
W
ORKS
Name
Profile SNVT Type SNVT
Index
SNVT Size SCPT_Reference SCPT
Index
nvoCapacityLim (output) Chiller lev_percent 81
two bytes NA
NA
Capacity Limit Setpoint - Network
This read/write network variable sets the maximum capacity level of the chiller. This level may be
adjusted via the BAS workstation or other network device, but cannot be adjusted above a factory-
specified limit. The default is 100%.
Measurement
Units
Data Type
Usable Range
Default Value
Percent of maximum
capacity
% BACnet:
Real
L
ON
W
ORKS
: Fixed-Point Scalar
signed long
0% to 100%
100%
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
2
3
Present Value
85
Object Name
NetworkCapacityLimitPct
LonWorks
L
ON
W
ORKS
Name
Profile SNVT Type SNVT
Index
SNVT Size SCPT_Reference SCPT
Index
nviCapacityLim (input)
Chiller lev_percent 81
two bytes NA
NA