ED15117
35
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Device 8
Variable
Location 58
Object Name
Location
L
ON
W
ORKS
L
ON
W
ORKS
Name Profile SNVT Type SNVT Index SNVT Size
SCPT_Reference SCPT Index
nciLocation Chiller
str_asc
36
31 bytes
max
SCPT_location 17
Chiller Mode
Chiller Mode Setpoint – Unless the configuration parameter nciDefaults =1 Network (nviMode) is set
to match the configuration value (nciMode) upon unit controller power-up or loss of communication.
Loss of communications is determined by Receive Heartbeat (nciRCvHrtBt). If Receive Heartbeat is
greater than zero, then communication is lost if nviMode is not written to prior to expiration of the
Receive Heartbeat timer. Each time nviMode is written, the Receive Heartbeat timer is reset. If
Receive Heartbeat is set to 0, then this function is disabled and communication loss is never detected.
Measurement
Units
Data Type
Usable Range
Default Value
HVAC Mode
NA
Unsigned Integer
Enumerated
3 = Cool
L
ON
W
ORKS
L
ON
W
ORKS
Name Profile SNVT Type SNVT Index
SNVT Size
SCPT Reference
SCPT Index
nciMode Chiller
hvac_mode
108 one
byte
SCPT_HVACmode
74
Property Values
1 = Heat Mode
3 = Cool Mode
11 = Ice Mode
Chiller Mode Output
This read only network variable indicates the current operating mode of the chiller.
Measurement
Units
Data Type
Usable Range
Default Value
HVAC Mode
NA
BACnet: Unsigned Integer
L
ON
W
ORKS
: Fixed Point Scalar -
unsigned long
See Below
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Multi-state Value
19
2
Present Value
85
Object Name
ActiveMode
Property Values
1 = ICE
2 = COOL
3 = HEAT
L
ON
W
ORKS
The L
ON
W
ORKS
equivalent of this data point is part of the Chiller Status network variable.
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerStat Chiller chlr_status 127
3
bytes