ED15117
41
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
81
Present Value
85
Object Name
C1Comp1DischRefPressure
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCmpDisRefPres
McQuayChiller SNVT_press
30
two
bytes
*Note: The units for SNVT_press#US is inches of water column. To display units in psi the format must be changed to SNVT_press#US_psi.
Compressor Discharge Refrigerant Temperature
This read only network variable indicates the current refrigerant temperature discharged from the
compressor.
For BACnet, there is a separate variable for each compressor. L
ON
W
ORKS
uses the
Compressor Select variable.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar signed
long
-40°–257°F
-40°-125°
C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
63
Present Value
85
Object Name
C1Comp1DischargeTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCompDisTemp McQuayChiller SNVT_temp_p
105
two
bytes
Compressor Discharge Saturated Refrigerant Temperature
This read only network variable indicates the current saturated refrigerant temperature discharged from
the compressor.
There is a separate output for each compressor. L
ON
W
ORKS
uses the Compressor
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
signed long
-15°–185°F
-26.2°–85°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
26
Present Value
85
Object Name
C1Comp1DischSatRefTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCmpDisSRefTmp McQuayChiller
SNVT_temp_p
105
two
bytes