42
ED 15117
Compressor Percent RLA
This read only network variable indicates the current percent RLA for the compressor motor of the
compressor.
BACnet uses a separate variable for each compressor. L
ON
W
ORKS
Measurement
Units
Data Type
Usable Range
Default Value
Percent RLA
Percent RLA BACnet: Real
L
ON
W
ORKS
: Fixed-Point Scalar
signed long
0-150%
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
0
8
Present Value
85
Object Name
C1Comp1MotorCurrentPercent
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCompPercRLA McQuayChiller SNVT_lev_percent 81
two
bytes
Compressor Power
This read only network variable indicates the current power of the compressor motor. BACnet uses a
separate variable for each compressor. L
ON
W
ORKS
uses the Compressor Select variable.
Measurement
Units
Data Type
Usable Range
Default Value
Power kiloWatts
BACnet:
Real
L
ON
W
ORKS
: Unsigned Long
0-600 NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
45
Present Value
85
Object Name
C1Comp1Kilowatts
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoKilowattts McQuayChiller
SNVT_power_kilo 28
2
bytes
Compressor Run Hours
This read only network variable indicates the number of hours that the compressor motor has been
turned on. BACnet uses a separate variable for each compressor. L
ON
W
ORKS
Measurement
Units
Data Type
Usable Range
Default Value
Event Count
Hours
BACnet: Real
L
ON
W
ORKS
: Float Type unsigned
long
0 –999,999
NA