ED15117
45
Compressor Suction Refrigerant Temperature
This read only network variable indicates the current refrigerant temperature entering the compressor.
There is a separate output for each compressor. L
ON
W
ORKS
uses the Compressor Select variable.
Measurement
Units
Data Type
Usable
Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar signed long
-40°–257°F
-40°–125°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
105
Present Value
85
Object Name
C1Comp1SuctionTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoSuctionTemp McQuayChiller
SNVT_temp_p
105
two
bytes
Condenser Entering Water Temperature
This read only network variable indicates the current temperature of the water entering the condenser.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
L
ON
W
ORKS
: Fixed Point Scalar
signed long
-40 to 257°F
-40 to 125°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
3
Present Value
85
Object Name
EntCondWaterTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoEntCndWTemp Chiller temp_p
105
two
bytes
Condenser Flow Switch Status
This read only network variable indicates the status of the water flowing through the condenser.
Measurement
Units
Data Type
Usable Range
Default Value
Flow State
NA
BACnet: Enumerated
L
ON
W
ORKS
: Structure
See Below
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
1
Present Value
85
Object Name
CondWaterFlowStatus
Property Values
0 = No Flow (Inactive)
1 = Flow (Active)