46
ED 15117
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoChillerStat.cond_flow Chiller chlr_status 127
3
bytes
Property Values (Limited)
0 = No Flow
1 = Flow
Structure
typedef struct {
chiller_t
chlr_run_mode;
hvac_t
chlr_op_mode;
struct{
unsigned in_alarm :1;
// offset 0
unsigned run_enabled :1;
// offset 1
unsigned local :1;
// offset 2
unsigned limited :1;
// offset 3
unsigned chw_flow :1;
// offset 4
unsigned condw_flow :1;
// offset 5
/* The last two bits (offset 6) are not defined */
}
chlr_state;
} SNVT_chlr_status;
Condenser Leaving Water Temperature
This read only network variable indicates the current temperature of the water leaving the condenser.
Measurement
Units
Data Type
Usable Range
Default Value
Temperature
°F/°C
BACnet: Real
LonWorks: Fixed Point Scalar signed
long
-40 to 257°F
-40 to 125°C
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
4
Present Value
85
Object Name
LvgCondWaterTemp
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoLvgCndWTemp Chiller
temp_p
105
two
bytes
Condenser Pump Run Hours
This read only network variable indicates the number of hours that the pump motor has been turned on
(see Pump Select).
Measurement
Units
Data Type
Usable Range
Default Value
Event Count
NA
BACnet: Real
L
ON
W
ORKS
: Fixed-Point Scalar
signed long
0 –999,999
NA
BACnet
Pump #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Value
2
110
Present Value
85