48
ED 15117
Measurement
Units
Data Type
Usable Range
Default Value
Flow Volume
BACnet:
GPM or L/s
L
ON
W
ORKS
:
CFM
OR
L/
S
BACnet: Real
L
ON
W
ORKS
: Fixed Point
Scalar unsigned long
BACnet:0-10,001.55 GPM
0-631 L/S
L
ON
W
ORKS
:
0 to 1337.01
CFM (0 to 631 L/s)
NA
BACnet
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Analog Input
0
147
Present Value
85
Object Name
CondWaterFlowRate
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCondFlowRate McQuayChiller SNVT_flow
15
two
bytes
Condenser Pump Status
This read only network variable indicates if the pump has been commanded On or Off.
See Pump
Select.
Measurement
Units
Data Type
Usable Range
Default Value
Flow State
NA
BACnet: Enumerated
L
ON
W
ORKS
: Structure
See Below
NA
BACnet
Pump #1
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
11
Present Value
85
Object Name
CondPump1State
Property Values
0 = Pump Off Request
1 = Pump On Request
Pump #2
Object Identifier
Property Identifier
Object Type
Type Enumeration
Instance
Property Name
Property Enumeration
Binary Input
3
12
Present Value
85
Object Name
CondPump2State
Property Values
0 = Pump Off Request
1 = Pump On Request
L
ON
W
ORKS
L
ON
W
ORKS
Name
Profile
SNVT Type
SNVT Index
SNVT Size
nvoCndWPump
McQuayChiller
SNVT_switch
95
two bytes
Valid Range
State
Value
Pump Status
0
unused
Pump Commanded Off
1
unused
Pump Commanded On