Wiring
[Method of Mounting Conduit]
•
When connecting indoor units for 3 rooms or more, open knockout holes without deforming the conduit mounting plate.
1) Dismount the service lid by removing the 2 screws.
2) Slide the protection plate up and remove it.
3) Pass wires through the conduit and secure them with a lock nut.
Stop valve cover
Service lid
Conduit mounting plate
Protection plate
Lock nut
Conduit
mounting plate
Conduit
Knockout holes
[Wiring procedure]
1) Strip the insulation from the wire (3/4inch (20mm)).
2) Connect the inter-unit wires between the indoor and
outdoor units
so that the terminal numbers match.
Tighten the terminal screws securely. It is recommended
that a slot-head screwdriver be used to tighten the
screws.
3) Be sure to match the symbols for wiring and piping.
4) Pull the wire lightly to make sure that it does not
disconnect.
5) Pass the wiring through the cutout on the bottom of the
protection plate and attach the protection plate.
6) After completing the work, reattach the service lid to its
original position.
Outdoor unit
60Hz 208/230V
To room B
To room C
To room D
Room
A
Room A
Room
C
Room
D
Room
B
Indoor unit
power supply
Follow local codes
for wiring and safety
devices between
outdoor unit and
power source.
Recommend using AWG14, stranded and
insulated wire for connections between indoor
and outdoor units.
Local code always supersedes recommendation.
Note: Take care to ensure that all wiring
between indoor unit and outdoor unit has a
consistent connection. Any splices can
cause communication errors.
Ground
Room A
Room C
Room D
Room B
power supply
Shape the wires so that there is
no lifting of the protection plate
or other structural parts.
Use the specified wires and
connect them securely.
Ground
This air conditioner must be grounded. For grounding, follow all local, and state electrical codes.