background image

3

n

English

Indoor/Outdoor Unit 

Installation Drawings

For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)

 CAUTION

• Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the 

indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See “Precautions for Laying Refrigerant Piping” on page 9 for details.

• It is impossible to connect the indoor unit for one room only. 

Be sure to connect at least 2 rooms

.

(Hole pitch of f

oot bolts)

574

(Hole pitch of 

foot bolts)

311

250mm from w

all

Allow space for piping 
and electrical servicing.

Level mounting base 
(optional parts)

Clamping material

Insulation tube

Service lid

Tape

Also insulate the connection on the outdoor unit.

Use tape or insulating material on all connections 
to prevent air from getting in between the copper 
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed 
above.

Cut thermal insulation 
pipe to an appropriate 
length and wrap it with 
tape, making sure that no 
gap is left in the insulation 
pipe’s cut line.

Wrap the insulation 
pipe with the finishing 
tape from bottom to top.

Caulk 
pipe hole 
gap 
with putty. 

Allow 300mm of 
work space below 
the ceiling surface.

If there is the danger of the unit falling 
or overturning, fix the unit with 
foundation bolts, or with wire or other 
means.

If the location does not have good 
drainage, place the unit on a level 
mounting base (or a plastic pedestal). 
Install the outdoor unit in a level 
position. Failure to do so may result in 
water leakage or accumulation.

Stop valve cover

Wire

unit: mm

Summary of Contents for 2MXS40H3V1B2

Page 1: ...English T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A...

Page 2: ...Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 0...

Page 3: ......

Page 4: ...f the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refriger...

Page 5: ...f sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot...

Page 6: ...ng base optional parts Clamping material Insulation tube Service lid Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from gettin...

Page 7: ...ation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundati...

Page 8: ...formance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 9: ...e of the flare Use refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the f...

Page 10: ...pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does go back this may indicate the presence of...

Page 11: ...refrigerant may slowly leak out do not leave the flare nut removed for a long period of time Do not overfill with refrigerant This will break the compressor Filling a cylinder with an attached siphon...

Page 12: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 13: ...inuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 14: ...e sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the...

Page 15: ...bend the electric box hook 4 Remove the lower electric box cover 5 Cut the jumper J3 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAUTION...

Page 16: ...t the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when th...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P401524 1 2015 02 Copyright 2015 Daikin...

Reviews: