7 Configuration

Installation manual

25

ETVH/9W
Daikin Altherma 3 H HT F
4P644728-1 – 2021.02

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent curves. Also see 

"7.3 Weather-dependent curve"

 [

4

 25].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.7

Configuration wizard: Tank

INFORMATION

To make tank defrost possible, we recommend a minimum
tank temperature of 35°C.

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

#

Code

Description

[5.6]

[6-0D]

Heat up mode

:

▪ 0: 

Reheat 

only

:  Only  reheat

operation is allowed.

▪ 1: 

Sc reheat

: The domestic

hot water tank is heated according to a
schedule  and  between  the  scheduled
heat  up  cycles,  reheat  operation  is
allowed.

▪ 2: 

Schedule  only

:  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

See the operation manual for more details.

Comfort setpoint

Only  applicable  when  domestic  hot  water  preparation  is 

Schedule

only

 or 

Sc reheat

. When programming the schedule, you

can make use of the comfort setpoint as a preset value. When you
later  want  to  change  the  storage  setpoint,  you  only  have  to  do  it  in
one place.

The  tank  will  heat  up  until  the 

storage  comfort  temperature

  has

been  reached.  It  is  the  higher  desired  temperature  when  a  storage
comfort action is scheduled.

Additionally, a storage stop can be programmed. This feature puts a
stop  to  tank  heating  even  if  the  setpoint  has  NOT  been  reached.
Only  program  a  storage  stop  when  tank  heating  is  absolutely
undesirable.

#

Code

Description

[5.2]

[6-0A]

Comfort setpoint

:

▪ 30°C~[6‑0E]°C

Eco setpoint

The 

storage  economic  temperature

  denotes  the  lower  desired

tank  temperature.  It  is  the  desired  temperature  when  a  storage
economic action is scheduled (preferably during day).

#

Code

Description

[5.3]

[6-0B]

Eco setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Reheat setpoint

Desired reheat tank temperature

, used:

▪ in 

Schedule 

reheat

  mode,  during  reheat  mode:  the

guaranteed  minimum  tank  temperature  is  set  by  the 

Reheat

setpoint

  minus  the  reheat  hysteresis.  If  the  tank  temperature

drops below this value, the tank is heated up.

▪ during  storage  comfort,  to  prioritize  the  domestic  hot  water

preparation.  When  the  tank  temperature  rises  above  this  value,
domestic  hot  water  preparation  and  space  heating/cooling  are
executed sequentially.

#

Code

Description

[5.4]

[6-0C]

Reheat setpoint

:

▪ 30°C~min(50,[6‑0E])°C

7.3

Weather-dependent curve

7.3.1

What is a weather-dependent curve?

Weather-dependent operation

The unit operates 'weather dependent' if the desired leaving water or
tank  temperature  is  determined  automatically  by  the  outdoor
temperature.  It  therefore  is  connected  to  a  temperature  sensor  on
the  North  wall  of  the  building.  If  the  outdoor  temperature  drops  or
rises, the unit compensates instantly. Thus, the unit does not have to
wait  for  feedback  by  the  thermostat  to  increase  or  decrease  the
temperature  of  the  leaving  water  or  tank.  Because  it  reacts  more
quickly,  it  prevents  high  rises  and  drops  of  the  indoor  temperature
and water temperature at tap points.

Advantage

Weather-dependent operation reduces energy consumption.

Weather-dependent curve

To  be  able  to  compensate  for  differences  in  temperature,  the  unit
relies on its weather-dependent curve. This curve defines how much
the  temperature  of  the  tank  or  leaving  water  must  be  at  different
outdoor  temperatures.  Because  the  slope  of  the  curve  depends  on
local circumstances such as climate and the insulation of the house,
the curve can be adjusted by an installer or user.

Summary of Contents for 3 H HT F

Page 1: ...datahub eu Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18EA6V ETVH16S23EA6V ETVH16S18EA9W ETVH16S23EA9W ETVX16S18EA6V ETVX16S23EA6V ETVX16S...

Page 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Page 3: ...nfiguration wizard 22 7 2 1 Configuration wizard Language 22 7 2 2 Configuration wizard Time and date 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configur...

Page 4: ...RNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Install the tundish away from any electrical device Possible consequence Ele...

Page 5: ...site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space cooling operation 5 35 C D...

Page 6: ...ollowing cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the...

Page 7: ...n hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximu...

Page 8: ...water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circul...

Page 9: ...are field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when...

Page 10: ...ol to air Types of glycol The types of glycol that can be used depend on whether the system contains a domestic hot water tank If Then The system contains a domestic hot water tank Only use propylene...

Page 11: ...10 X6M 2 45 10 X10M 0 88 10 6 3 Connections to the indoor unit Item Description Power supply main See 6 3 1 To connect the main power supply 412 Item Description Power supply backup heater See 6 3 2 T...

Page 12: ...AN cartridge Installer reference guide D Wireless gateway for room thermostat wired or wireless In case of See Wireless room thermostat Installation manual of the wireless room thermostat Addendum boo...

Page 13: ...connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit...

Page 14: ...Q1DI a b a Factory mounted cable connected to the contactor of the backup heater inside the switch box K5M b Field wiring see table below Model power supply Connections to backup heater power supply...

Page 15: ...ith transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 4 2 1 To open the indoor unit 45 1...

Page 16: ...he alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewiring between X2M 7 9 and Q1L...

Page 17: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the approp...

Page 18: ...able with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the...

Page 19: ...X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter...

Page 20: ...dle excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor unit 1 2...

Page 21: ...via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settin...

Page 22: ...tings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of domestic hot water tank is installed Emergency When the heat pump fails...

Page 23: ...ion N A E 0D Glycol Filled system Is the system filled with glycol 0 No 1 Yes 7 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity...

Page 24: ...crease the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controll...

Page 25: ...til the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a s...

Page 26: ...Go to the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or...

Page 27: ...he weather dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Add...

Page 28: ...2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Thermostat type Only applicable in external room thermostat control For...

Page 29: ...ectrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevent...

Page 30: ...ocal supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor u...

Page 31: ...the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test Backup heater 2 test Pump test INFORMATION Make sure that all air is purged before executing the t...

Page 32: ...ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system...

Page 33: ...ating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from out...

Page 34: ...reless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireles...

Page 35: ...ostat For safety thermostat For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally...

Page 36: ...2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wirele...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1 2021 02 Copyright 2021 Daikin 4P644728 1 0000000T Verantwortung f r Energie und Umwelt...

Reviews: