background image

8 Commissioning

Installation manual

30

ETVH/9W

Daikin Altherma 3 H HT F

4P644728-1 – 2021.02

8

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during the commissioning
and hand-over to the user.

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  must  remain  open  after
commissioning.

INFORMATION

Protective  functions  –  "Installer-on-site  mode"

.  The

software  is  equipped  with  protective  functions,  such  as
room antifrost. The unit automatically runs these functions
when necessary.

During  installation  or  service  this  behaviour  is  undesired.
Therefore, the protective functions can be disabled:

At  first  power-on:

  The  protective  functions  are

disabled by default. After 12 h they will be automatically
enabled.

Afterwards:

  An  installer  can  manually  disable  the

protective  functions  by  setting  [9.G]: 

Disable

protections

=

Yes

.  After  his  work  is  done,  he  can

enable  the  protective  functions  by  setting  [9.G]:

Disable protections

=

No

.

8.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

automatic air purge

 valves are open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water must come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions. See "To check the water volume and flow rate"
in 

"5.1 Preparing water piping"

 [

4

 8].

The 

domestic hot water tank

 is filled completely.

8.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"5.1  Preparing  water

piping"

 [

4

 8].

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

8.2.1

To check the minimum flow rate

1

Check the hydraulic configuration to find out which
space heating loops can be closed by mechanical,
electronic, or other valves.

2

Close all space heating loops that can be closed.

3

Start the pump test run (see 

"8.2.4 To perform an

actuator test run"

 [

4

 31]).

4

Read out the flow rate

(a)

 and modify the bypass valve

setting to reach the minimum required flow rate + 2 l/
min.

(a)

During pump test run, the unit can operate below the minimum
required flow rate.

Minimum required flow rate

25 l/min

Summary of Contents for 3 H HT F

Page 1: ...datahub eu Installation manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18EA6V ETVH16S23EA6V ETVH16S18EA9W ETVH16S23EA9W ETVX16S18EA6V ETVX16S23EA6V ETVX16S...

Page 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Page 3: ...nfiguration wizard 22 7 2 1 Configuration wizard Language 22 7 2 2 Configuration wizard Time and date 22 7 2 3 Configuration wizard System 22 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configur...

Page 4: ...RNING Field piping method MUST be in accordance with the instructions from this manual See 5 Piping installation 48 WARNING Install the tundish away from any electrical device Possible consequence Ele...

Page 5: ...site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space heating operation 5 30 C Space cooling operation 5 35 C D...

Page 6: ...ollowing cases 4 2 2 To lower the switch box on the indoor unit 46 4 3 2 To connect the drain hose to the drain 47 When you need access to the high voltage switch box 2 T25 5 If you need access to the...

Page 7: ...n hose to the drain See 4 3 2 To connect the drain hose to the drain 47 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maximu...

Page 8: ...water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circul...

Page 9: ...are field supplied NOTICE Overpressure bypass valve delivered as accessory We recommend to install the overpressure bypass valve in the space heating water circuit Mind the minimum water volume when...

Page 10: ...ol to air Types of glycol The types of glycol that can be used depend on whether the system contains a domestic hot water tank If Then The system contains a domestic hot water tank Only use propylene...

Page 11: ...10 X6M 2 45 10 X10M 0 88 10 6 3 Connections to the indoor unit Item Description Power supply main See 6 3 1 To connect the main power supply 412 Item Description Power supply backup heater See 6 3 2 T...

Page 12: ...AN cartridge Installer reference guide D Wireless gateway for room thermostat wired or wireless In case of See Wireless room thermostat Installation manual of the wireless room thermostat Addendum boo...

Page 13: ...connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit...

Page 14: ...Q1DI a b a Factory mounted cable connected to the contactor of the backup heater inside the switch box K5M b Field wiring see table below Model power supply Connections to backup heater power supply...

Page 15: ...ith transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 4 2 1 To open the indoor unit 45 1...

Page 16: ...he alarm output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HBAA is required b Prewiring between X2M 7 9 and Q1L...

Page 17: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the approp...

Page 18: ...able with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the...

Page 19: ...X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 B A B X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid contacts Wires Smart Grid pulse meter...

Page 20: ...dle excessive cable length with a cable tie 6 3 12 To connect the WLAN cartridge delivered as accessory 1 Insert the WLAN cartridge into the cartridge slot on the user interface of the indoor unit 1 2...

Page 21: ...via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For example 2 9 Accessing settings via the code in the overview field settin...

Page 22: ...tings E 05 Can the system prepare domestic hot water E 06 Is a domestic hot water tank installed in the system E 07 What kind of domestic hot water tank is installed Emergency When the heat pump fails...

Page 23: ...ion N A E 0D Glycol Filled system Is the system filled with glycol 0 No 1 Yes 7 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity...

Page 24: ...crease the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controll...

Page 25: ...til the storage comfort temperature has been reached It is the higher desired temperature when a storage comfort action is scheduled Additionally a storage stop can be programmed This feature puts a s...

Page 26: ...Go to the next temperature Confirm changes and proceed 7 3 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or...

Page 27: ...he weather dependent curve Zone Go to Main zone Heating 2 5 Main zone Heating WD curve Main zone Cooling 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Add...

Page 28: ...2 2 contacts The used external room thermostat can send a separate heating cooling thermo ON OFF condition 7 4 2 Additional zone Thermostat type Only applicable in external room thermostat control For...

Page 29: ...ectrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevent...

Page 30: ...ocal supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicable Between the indoor u...

Page 31: ...the menu go to Stop test run 2 Select OK to confirm Possible actuator test runs Backup heater 1 test Backup heater 2 test Pump test INFORMATION Make sure that all air is purged before executing the t...

Page 32: ...ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system...

Page 33: ...ating cooling Water IN screw connection 1 a2 Space heating cooling Water OUT screw connection 1 b1 DHW Cold water IN screw connection 3 4 b2 DHW Hot water OUT screw connection 3 4 c1 Water IN from out...

Page 34: ...reless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireles...

Page 35: ...ostat For safety thermostat For safety thermostat For safety thermostat For smartgrid For Smart Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally...

Page 36: ...2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wirele...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1 2021 02 Copyright 2021 Daikin 4P644728 1 0000000T Verantwortung f r Energie und Umwelt...

Reviews: