Page 4 of 6 / IM 955-3

Utility Box Mounting of Sensor 669529001

1.  Feed the cable from the utility box.
2.  Strip 1/4–inch of insulation from the end of the wires.
3.  Connect stripped, labeled wires to matching terminals on 

the temperature sensor base. See 

Figure 2

.

4.  Tighten screws on terminal connections. Gently tug wire 

to check for secure connections. Confirm that each wire 

is connected to the proper terminal.

5.  Neatly store excess wire back inside the utility box.
6.  Mount the sensor base to the utility box using two 6-32 × 

5/8–inch flat head sheet metal screws  

provided with the sensor.

7.  Replace cover on wall temperature sensor by attaching 

the catches at the top of the cover to the top tabs on the 

sensor base. Secure the cover to the base by tightening 

the two allen wrench set-screws on the bottom of the 

sensor cover. Do not overtighten.

Wiring

Temperature Sensors 669529101 & 

669529201 

Note:

  All sensors have black (common), white (thermistor), 

and red (LED) wires. With the tenant override and/or 

set point adjustment option, a green wire is provided. 

The optional thermometer does not affect wiring.

Figure 1: Temperature Sensor Wiring to MicroTech III Unit 

Controller

Temperature 

Sensor Terminals 

MicroTech III Unit Con

-

troller TB1 Terminals 

Temperature Sensor 669529001

Figure 2: Temperature Sensor Wiring to MicroTech III Unit 

Controller

MicroTech III Unit Con

-

troller TB1 Terminals 

Temperature 

Sensor Terminals 

Testing

Temperature Sensors 669529101 & 

669529201

Cool Test

1.  Slide Mode switch to Cool mode. 
2.  Adjust set temperature so it is 5 degrees below room 

temperature. 

3.  Air conditioning should come on within five (5) minutes. 

Status indicator may come on.

4.  Adjust the set temperature 2 degrees above the room 

temperature and the A/C should turn off. There may be a 

fan delay on your system.

Heat Test

1.  Slide Mode switch to Heat mode.
2.  Adjust the set temperature so it is 5 degrees above the 

room temperature.

3.  Heat should come on within five (5) minutes. Status 

indicator may come on. 

4.  Adjust the set temperature so it is 2 degrees below the 

room temperature and the heat should turn off. There 

may be a fan delay on your system.

Fan Test

1.  Set room temperature so that unit is no longer heating or 

cooling the space. Wait for unit to cycle off.  

2.  Slide Fan switch to On position.
3.  Indoor fan turns on.
4.  Slide Fan switch to Auto position. 
5.  Indoor fan turns off.

Summary of Contents for 669529101

Page 1: ...ce Heat Pump Wall Mounted Room Temperature Sensors Sensor Kit P N 669529101 669529201 669529001 Group WSHP Part Number 910144730 Date October 2013 IM 955 3 Sensor 669529101 Sensor 669529201 Sensor 669529001 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Page 2: ...Microtech III Wall Mounted Room Tem perature Sensor For installation and commissioning instructions and general information on a particular unit refer to its model specific installation manual Table 1 MicroTech III Sensor Kits Water Source Heat Pump 10 kW Sensor Kit P N Tenant Override Button SPT Adj Pot Status LED Fan and Mode Switches 669529001 Yes No Yes No 669529101 Yes Yes Yes Yes 55º to 95ºF...

Page 3: ...njury or death 1 Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to the OFF position 2 Remove the sensor cover by inserting a screwdriver and gently twisting it in the slots on the sides of the wall temperature sensor 669529101 669529201 only To remove the cover on sensor 669529001 loosen two allen wrench set screws located on the undersid...

Page 4: ...ot affect wiring Figure 1 Temperature Sensor Wiring to MicroTech III Unit Controller Temperature Sensor Terminals MicroTech III Unit Con troller TB1 Terminals Temperature Sensor 669529001 Figure 2 Temperature Sensor Wiring to MicroTech III Unit Controller MicroTech III Unit Con troller TB1 Terminals Temperature Sensor Terminals Testing Temperature Sensors 669529101 669529201 Cool Test 1 Slide Mode...

Page 5: ...ve 5 minutes Status indicator may come on 3 Using the BMS adjust the set temperature 2 degrees above the room temperature and the A C should turn off There may be a fan delay on your system Table 2 WSHP Unit Status LED Definitions Status LED Unit Status Unit Operation ON OFF 0 5 seconds 0 5 seconds Controller Off or Network Wink operation active Alarm 0 0 seconds Continuous Unit running in Night S...

Page 6: ...s at www DaikinAP com and click on Training or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services...

Reviews: