background image

M

ounting

, M

AintenAnce

, t

erMinAtions

Mounting

Location

Avoid mounting on outside walls or in direct sunlight.

Junction Box, (J-Box)

1.  Pull the wire through the wall and out of the junction box, 

leaving about six inches free.

2.  Pull the wire through the hole in the base plate.
3.  Secure the back plate to the box using the #6-32 × 1/2 inch 

mounting screws provided.

4.  Screw the plate firmly to the wall so the foam plate backing 

is compressed about 50%.

5.  Terminate the unit according to the guidelines in the 

termination section.

6.  Attach cover by latching it to the top of the base, rotating it 

down and snapping into place.

7.  Secure the cover by backing out the lock-down screws 

using a 1/16" Allen wrench until it is flush with the bottom of 

the cover.

Figure 2: Junction box mounting (hardware is provided for 

both junction box and drywall installation.)

Cover lockdown screws 1/16" allen

Mounting base plate

Drywall mounting

1.  Place the base plate against the wall where you want to 

mount the sensor.

2.  Mark out the two mounting holes where the unit will be 

attached to the wall. Drill a 3/16" hole in the center of each 

mounting hole and insert a drywall anchor into the holes.

3.  Drill one 1/2" hole in the middle of the marked wiring 

through hole area.

4.  Pull the wire through the wall and out the 1/2" hole, leaving 

about six inches free.

5.  Pull the wire through the hole in the base plate.
6.  Secure the base to the drywall anchors using the #6 × 1" 

mounting screws provided.

7.  Screw the plate firmly to the wall so the foam plate backing 

is compressed about 50%.

8.  Terminate the unit according to the guidelines in the 

termination section.

9.  Attach cover by latching it to the top of the base, rotating it 

down and snapping it into place.

10. Secure the cover by backing out the lock-down screws 

using a 1/16" Allen wrench until it is flush with the sides of 

the cover

Note:

   in any wall-mount application, the wall temperature 

and the temperature of the air within the wall cavity can 

cause erroneous readings.

 

The mixing of room air and air from within the wall 

cavity can lead to condensation, erroneous readings 

and sensor failure. To prevent these conditions, Daikin 

recommends sealing the conduit leading to the junction 

box with fiberglass.

Maintenance

Wipe as needed with a damp water only cotton cloth. Do not 

paint.

Terminations

Daikin Applied recommends using shielded 22AWG for all 

connections and a separate  twisted pair for the power wire 

connections. The shield should be earth grounded only at the 

power source. Larger gauge wire may be required for runs 

greater than 250'. 

Note:  Three conductors are required for the basic sensor 

910247450, and four conductors are required for the 

basic sensor with cool to warm 910247453.

Figure 3: Basic sensor circuit boards

SW1

J1

D1

R1

A

2

4    

3

1  (ST)

4  (UTS)

5  (GND)

 

Sensor 910247450 

Sensor 910247453

All wiring must comply with the National Electric Code (NEC) 

and local codes. Do NOT run any of this device’s wiring in the 

same conduit as other AC power wiring. Tests show that fluctu-

ating and inaccurate signal levels are possible when AC power 

wiring is present in the same conduit as the signal lines. If you 

are experiencing any of these difficulties, please contact your 

Daikin representative.

www.DaikinApplied.com 

IM 1277

Summary of Contents for 910247450

Page 1: ...perature adjustment Basic room sensor buttons dimensions Figure 1 Basic room sensors for Unit Ventilator units P N 910247450 910247453 4 50 2 86 1 13 LED Status Indicator Override Reset LED Status Indicator Override Reset 2 86 4 50 1 13 Sensor 910247450 Sensor 910247453 Installation and Maintenance Manual IM 1277 Group UV Part Number 910247365 Date October 2018 Basic Room Sensors Used with Unit Ve...

Page 2: ...r Models UAZ UAE UAR UGR Basic room sensor s functions Unit ventilator models The Basic Sensor with setpoint adjustment PN 910247453 requires 4 wires The Basic Sensor PN 910247450 requires 3 wires Specifications Sensor Temperature 10K 2 Thermistor 0 36ºF 0 2ºC Outputs Temperature 4 Analog thermistor resistance Sensor controls Termination Terminals 16 to 22 AWG Mounting Standard 2 4 J box or drywal...

Page 3: ...ompressed about 50 8 Terminate the unit according to the guidelines in the termination section 9 Attach cover by latching it to the top of the base rotating it down and snapping it into place 10 Secure the cover by backing out the lock down screws using a 1 16 Allen wrench until it is flush with the sides of the cover Note in any wall mount application the wall temperature and the temperature of t...

Page 4: ... terminal locations 1 ST Status indicator input from the MicroTech unit control ler 5VDC 3 SP Setpoint Adjustment used with sensor 910247453 only 4 UTS Output signal room temp thermistor sensor 10K ATP Z curve 10K 2 5 GND Ground or neutral Common reference for all signal terminals Note Resistance measurements between terminals 4 5 can be compared to those in Table 3 Table 2 Unit ventilator MicroTe...

Reviews: