Controller Inputs and Outputs
Main Controller
Table 22: Analog Inputs
#
Description
Signal Type
Expected Range
AI1
Evaporator EWT
NTC 10k
340 to 300k Ω
AI2
Evaporator LWT
NTC 10k
340 to 300k Ω
AI3
Ambient Temp
NTC 10k
340 to 300k Ω
X1
Demand Limit
4-20 mA
1 to 23 mA
X4
LWT Reset
4-20 mA
1 to 23 mA
Table 23: Analog Outputs
#
Description
Signal Type Range
X2
Circuit 1 Fan VFD Speed2 Voltage
0 to 10 volts
X3
Circuit 2 Fan VFD Speed2 Voltage
0 to 10 volts
X5
Circuit 1 Fan VFD Speed1 Voltage
0 to 10 volts
X6
Circuit 2 Fan VFD Speed1 Voltage
0 to 10 volts
Table 24: Digital Inputs
Description
Signal Off
Signal On
DI1
External Alarm/Event
Ext. Fault
No Ext. Fault
DI2
Evaporator Flow Switch No Flow
Flow
DI3
Double Set Point/ Mode
Switch
See sections on Unit Mode
Selection and LWT Target
DI4
Remote Switch
Remote Disable Remote Enable
DI5
Unit Switch
Unit Disable
Unit Enable
Table 25: Digital Outputs
Description
Output Off
Output On
DO1 Evaporator Water Pump 1 Pump Off
Pump On
DO2 Alarm Indicator
Alarm Not Active Alarm Active
DO3 Circuit 1 Fan Output 1
Fan(s) Off
Fan(s) On
DO4 Circuit 1 Fan Output 2
Fan(s) Off
Fan(s) On
DO5 Circuit 1 Fan Output 3
Fan(s) Off
Fan(s) On
DO6 Circuit 1 Fan Output 4
Fan(s) Off
Fan(s) On
DO7 Circuit 2 Fan Output 1
Fan(s) Off
Fan(s) On
DO8 Circuit 2 Fan Output 2
Fan(s) Off
Fan(s) On
DO9 Circuit 2 Fan Output 3
Fan(s) Off
Fan(s) On
DO10 Circuit 2 Fan Output 4
Fan(s) Off
Fan(s) On
X7
Circuit 1 Condenser SV 1 Solenoid Closed Solenoid Open
X8
Circuit 2 Condenser SV 1 Solenoid Closed Solenoid Open
Compressor Module 1
Table 26: Analog Inputs
Description
Signal Type Expected Range
X1
Circuit 1 Suction Temp
NTC 10k
340 to 300k Ω
X2
Circuit 1 Evaporator Press Voltage
0.4 to 4.6 volts
X4
Circuit 1 Condenser Press Voltage
0.4 to 4.6 volts
Table 27: Digital Inputs
Description
Signal Off
Signal On
X6
Circuit 1 Switch
Circuit Disable Circuit Enable
X7
Circuit 1 MHP Switch
Fault
No fault
X8
Circuit 1 Motor
Protection
Fault
No fault
DI1
Circuit 1 (or Unit) PVM/
GFP
Fault
No fault
NOTE:
The Motor Protection and MHP input signal are wired
in series. If Motor Protection input is open, MHP
Switch input will also be open.
Table 28: Digital Outputs
Description
Output Off
Output On
DO1
Compressor #1
Compressor Off
Compressor On
DO2
Compressor #3
Compressor Off
Compressor On
DO3
Compressor #5
Compressor Off
Compressor On
DO4
Evaporator Water
Pump 2
Pump Off
Pump On
DO5
Circuit 1 Hot Gas
Bypass SV
Solenoid Closed
Solenoid Open
DO6
Circuit 1 Liquid
Line SV
Solenoid Closed
Solenoid Open
Compressor Module 2
Table 29: Analog Inputs
Description
Signal Type
Expected
Range
X1
Circuit 2 Suction Temp
NTC 10k
340 to 300k Ω
X2
Circuit 2 Evaporator
Press
Voltage
0.4 to 4.6 volts
X4
Circuit 2 Condenser
Press
Voltage
0.4 to 4.6 volts
Table 30: Digital Inputs
Description
Signal Off
Signal On
X6
Circuit 2 Switch
Circuit Disable
Circuit Enable
X7
Circuit 2 MHP Switch
Fault
No fault
X8
Circuit 2 Motor
Protection
Fault
No fault
DI1
Circuit 2 PVM/GFP
Fault
No fault
NOTE:
The Motor Protection and MHP input signal are wired
in series. If Motor Protection input is open, MHP
Switch input will also be open (not applicable to 030
and 045E models).
Table 31: Digital Outputs
Description
Output Off
Output On
DO1 Compressor #2
Compressor Off Compressor On
DO2 Compressor #4
Compressor Off Compressor On
DO3 Compressor #6
Compressor Off Compressor On
DO5 Circuit 2 Hot Gas Bypass
SV
Solenoid Closed Solenoid Open
DO6 Circuit 2 Liquid Line SV
Solenoid Closed Solenoid Open