40
IOM 1206-1
Unit Controller Operation
Circuit Functions
Definitions
Refrigerant Saturated Temperature
Refrigerant saturated temperature shall be calculated from the
pressure sensor readings for each circuit.
Evaporator Approach
The evaporator approach shall be calculated for each circuit.
The equation is as follows:
Evaporator Approach = LWT – Evaporator
Saturated Temperature
Condenser Approach
The condenser approach shall be calculated for each circuit.
The equation is as follows:
Condenser Approach = Condenser Saturated
Temperature - OAT
Suction Superheat
Suction superheat shall be calculated for each circuit using the
following equation:
Suction superheat = Suction Temperature –
Evaporator Saturated Temperature
Pumpdown Pressure
The pressure to which a circuit will pumpdown is based on the
Low Evaporator Pressure Unload set point. The equation is as
follows:
Pumpdown pressure = Low Evap Pressure Unload
set point – 103KPA (15 PSI)
Circuit Control Logic
Circuit Enabling
A circuit should be enabled to start if the following conditions
are true:
•
Circuit switch is closed
•
No circuit alarms are active
•
Circuit Mode set point is set to Enable
•
At least one compressor is enabled to start (according to
enable setpoints)
Compressor Availability
A compressor is considered available to start if all the
following are true:
The corresponding circuit is enabled
•
The corresponding circuit is not in pumpdown
•
No cycle timers are active for the compressor
•
No limit events are active for the corresponding circuit
•
The compressor is enabled via the enable setpoints
•
The compressor is not already running
Circuit States
The circuit will always be in one of four states:
Off – Circuit is not running
Preopen – Circuit is preparing to start
Run – Circuit is running
Pumpdown – Circuit is doing a normal shutdown
Transitions between these states are shown in the following
diagram.
T1 – Off to Preopen
•
No compressors are running and any compressor on circuit
is commanded to start (see unit capacity control)
T2 – Preopen to Run
•
5 seconds has passed
OFF
RUN
PUMPDOWN
T 3
T2
T4
T 1
POWER
ON
T5
PREOPEN
T 6