26
IOM 1206-1
Unit Controller Operation
EXV Module 1 and 2
These modules will be used only when the expansion
valve type is electronic.
Table 31: Digital Outputs
Table 32: Stepper Motor Output
RapidRestore
®
This module will be used only when the unit is equipped with
the RapidRestore option.
Table 33: Digital Inputs
Sensor Information
Temperature
All temperature sensors will be Daikin part number 1934146.
Pressure
Pressure inputs will be read using 0 to 5 volt ratiometric
sensors. Nominal voltage range will be 0.5 to 4.5 volts.
Pressure on the low side will be measured using Daikin part
number 331764501.
Pressure on the high side will be measured using Daikin part
number 331764601.
Description
Output Off
Output On
DO1
Circuit 1 Fan Output 5
Fan(s) Off
Fan(s) On
Description
M1+, M1-
EXV Stepper Coil 1
M2+, M2-
EXV Stepper Coil 2
Description
Signal Off
Signal On
DI1
RapidRestore Enable
Disable RapidRestore
Allow RapidRestore
Enabling
DI2
Backup Chiller
Designation
Not Backup Chiller
Backup Chiller