background image

3

DAR0904 Temperature Rise Table (Degrees F)

208

240

480

2800

14

19

19

2900

14

18

18

3000

13

18

18

3100

13

17

17

3200

12

17

17

2800

19

25

25

2900

18

24

24

3000

18

24

24

3100

17

23

23

3200

17

22

22

2800

28

38

38

2900

27

37

37

3000

27

35

35

3100

26

34

34

3200

25

33

33

Airhandler

Heat Kit 

KW

CFM

Supply Voltage

15

20

DAR0904 

Tempera ture 

Ri s e Ta bl e 

(Degrees  F)

30

Table 4.

DAR1204 Temperature Rise Table (Degrees F)

208

240

480

3800

10

14

14

3900

10

14

14

4000

10

13

13

4100

10

13

13

4200

9

13

13

3800

14

19

19

3900

14

18

18

4000

13

18

18

4100

13

17

17

4200

13

17

17

3800

21

28

28

3900

20

27

27

4000

20

27

27

4100

19

26

26

4200

19

25

25

CFM

Supply Voltage

DAR1204

Tempera ture 

Ri s e Ta bl e 

(Degrees  F)

15

20

30

Airhandler

Heat Kit 

KW

Table 5.

NOTE:

  Table 5 is calculated with both stages of electric heat en-

gaged (2 stage heat systems). For systems using staged electric
heat, divide the temperature rise from the table by 2 for 1

st

 stage

operation.

E

LECTRICAL

 S

UPPLY

 W

IRE

 

AND

 MOP

T

O

 

AVOID

 

THE

 

RISK

 

OF

 

FIRE

 

OR

 

EQUIPMENT

 

DAMAGE

USE

 

COPPER

 

CONDUCTORS

 

ONLY

.

WARNING

T

O

 

AVOID

 

PROPERTY

 

DAMAGE

PERSONAL

 

INJURY

 

OR

 

DEATH

 

DUE

 

TO

 

ELECTRICAL

 

SHOCK

THIS

 

UNIT

 MUST 

HAVE

 

AN

 , 

 

ELECTRICAL

 

GROUND

.  T

HE

 

ELECTRICAL

 

GROUND

 

CIRCUIT

 

MAY

 

CONSIST

 

OF

 

AN

 

APPROPRIATELY

 

SIZED

 

ELECTRICAL

 

WIRE

 

CONNECTING

 

THE

 

GROUND

 

LUG

 

IN

 

THE

 

UNIT

 

CONTROL

 

BOX

 

TO

 

THE

 

BUILDING

 

ELECTRICAL

 

SERVICE

 

PANEL

.

O

THER

 

METHODS

 

OF

 

GROUNDING

 

ARE

 

PERMITTED

 

IF

 

PERFORMED

 

IN

 

ACCORDANCE

 

WITH

 

THE

 N

ATIONAL

 E

LECTRIC

 C

ODE

 (NEC)/A

MERICAN

 

N

ATIONAL

 S

TANDARDS

 I

NSTITUTE

 (ANSI)/N

ATIONAL

 F

IRE

 

P

ROTECTION

 A

SSOCIATION

 (NFPA) 70 

AND

 

LOCAL

/

STATE

 

CODES

. I

N

 

C

ANADA

ELECTRICAL

 

GROUNDING

 

IS

 

TO

 

BE

 

IN

 

ACCORDANCE

 

WITH

 

THE

 

C

ANADIAN

 E

LECTRIC

 C

ODE

 (CSA) C22.1.

UNINTERRUPTED

UNBROKEN

WARNING

INSPECTION OF THE BUILDING ELECTRICAL SERVICE.
T

HIS

 

UNIT

 

IS

 

DESIGNED

 

FOR

 3-

PHASE

 

OPERATION

. DO NOT OPERATE 

ON A SINGLE PHASE POWER SUPPLY.  SEE THE “WARNING“ 
ABOVE.
M

EASURE

 

THE

 

POWER

 

SUPPLY

 

TO

 

THE

 

UNIT

. T

HE

 

SUPPLY

 

VOLTAGE

 

MUST 

BE

 

IN

 

AGREEMENT

 

WITH

 

THE

 

UNIT

 

NAMEPLATE

 

POWER

 

REQUIREMENTS

 

AND

 

WITHIN

 

THE

 

RANGE

 

SHOWN

 

IN

 T

ABLE

 6.

WARNING

Building Electrical Service Inspection

This unit is designed for 3-phase operation.  

DO NOT OPERATE

ON A SINGLE PHASE POWER SUPPLY.  SEE THE PRECEDING
WARNING.

 Measure the power supply to the unit.  The supply

voltage MUST be in agreement with the unit nameplate power
requirements and within the range shown in Table 6.

Minimum Supply

Maximum Supply

Voltage

Voltage

208 – 230

187

253

460

414

506

Nominal

Table 6.

Voltage Balance  The supply voltage shall be unbalance (phase to
phase) within 2%.  To calculate the percentage of voltage unbalance
use the following formula:

Percentage

                 Max Voltage Deviation From Avg     Volt-

age Unbalance            = 100  x

 Average Voltage

Example

.

L1 – L2 = 220 V
L2 – L3 = 216 V
L1 – L3 = 213 V

Avg. Voltage

        =

(220+216+213) / 3
     =

 649 / 3

     =

216

Max. Deviation from Avg. = 220 – 216 = 4

% Voltage Unbalance

=   100 x (4 / 216)
=   400 / 216
=   1.8%

Summary of Contents for AHKD 20

Page 1: ...ised by freight damage Check the unit model number specifications and electrical char acteristics to determine if they are correct In the event an incor rect unit is shipped it must be returned to the supplier and must NOT be installed The manufacturer assumes no responsibility for installation of incorrectly shipped units REPLACEMENT PARTS ORDERING PARTS When reporting shortages or damages or ord...

Page 2: ...g local codes regulations is the responsibility of the in staller The manufacturer assumes no responsibility for equip ment installed in violation of any codes or regulations PRE INSTALLATION INSTRUCTIONS Carefully read all instructions for the installation prior to install ing product Make sure each step or procedure is understood and any special considerations are taken into account before start...

Page 3: ...HE BUILDING ELECTRICAL SERVICE PANEL OTHER METHODS OF GROUNDING ARE PERMITTED IF PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE NEC AMERICAN NATIONAL STANDARDS INSTITUTE ANSI NATIONAL FIRE PROTECTION ASSOCIATION NFPA 70 AND LOCAL STATE CODES IN CANADA ELECTRICAL GROUNDING IS TO BE IN ACCORDANCE WITH THE CANADIAN ELECTRIC CODE CSA C22 1 UNINTERRUPTED UNBROKEN WARNING INSPECTION OF THE BUIL...

Page 4: ... Use Table 8 to de termine the voltage drop per foot of various conductors Wire Size AWG 10 15 20 25 30 35 40 45 14 75 50 37 NR NR NR NR NR 12 118 79 59 47 NR NR NR NR 10 188 125 95 75 63 54 NR NR 8 301 201 150 120 100 86 75 68 6 471 314 235 188 157 134 118 110 Based on NEC 1996 Max Allowable Length in Feet to Limit Voltage Drop to 2 Min Circuit Ampacity MCA Table 8 MAXIMUM OVERCORRECT PROTECTION ...

Page 5: ... the kW The supply voltage is to be installed on the terminal block located in the heater kit control box The heater kit is factory equipped with the supply and low volt age wires for the air handler The low voltage connection from the heater kit is provided through a multi pin plug which con nects to a mating plug in the air handler The high voltage con nections are to be made at the air handler ...

Page 6: ... Single Stage Heat Single Stage Cooling where R Red W White G Green BL Blue Note Brown wire is not used and is to be taped Figure 6 Two Stage Heat Single Stage Cooling where R Red W White BR Brown G Green BL Blue ...

Page 7: ...Terminal Block HC Heater Contactor HTR Heater Element PLS Primary Limit Switch SLS Secondary Limit Switch L3 L1 L2 Wiring is subject to change always refer to the wiring diagram on the unit for the most up to date wiring WARNING WIRING DIAGRAM ...

Page 8: ...ays refer to the wiring diagram on the unit for the most up to date wiring WARNING WIRING DIAGRAM L3 L2 L1 Legend FR Fan Relay FU Fuse TB Terminal Block HC Heater Contactor HTR Heater Element PLS Primary Limit Switch SLS Secondary Limit Switch ...

Reviews: