8
Installation
Pr
ocedure
Installation
Different-voltage model (–E)
Power cable insertion
hole (
φ
28)
Top plate mounting screw
Top plate
Transformer box
For inside of the electrical
equipment box, refer to the top
view of the electrical equipment
box in “
Outline of electrical
equipment box
” (page ).
9
To use an earth leakage breaker, select an inverter-compatible type.
If the earth leakage breaker is not inverter-compatible, it may malfunction due to high-frequency noise of the
inverter. (Recommended product: 15 mA or 20 mA)
(1) (4)
(3)
Different-voltage
model (–E)
(2)
Standard model,
–B, –C, –H
(2)
Mounting a circuit breaker
Wiring procedure
∗
Mount a circuit breaker exclusively for the Oil Cooling Unit.
The Oil Cooling Unit is not equipped with a circuit breaker. Be sure to mount a 3-pole circuit breaker exclusively for the Oil
Cooling Unit to the main machine. For the breaker capacity, refer to the specifications of each model (see page ).
To ensure safety, it is recommended to use an earth leakage breaker.
12·13
CAUTION
To connect each cable, use M4 (AKZJ908: M5) shielded round crimp
terminal.
Place the power cable in a conduit.
For
remote control input connecting
procedure, refer to page .
For
external output contact connecting
procedure, refer to page .
Re-mount the top plate, and fasten it with the
screws.
4
9
10
Remove the top plate mounting screws, and
remove the top plate.
1. Insert the power cable into the power cable
insertion hole (
φ
28) in the side plate of the unit.
When using the different-voltage model (–E),
insert the power cable into the transformer box.
2. Insert the remote control signal cable and
external output signal cable into the signal cable
insertion hole (
φ
22) in the side plate of the unit.
Connect the power cable to the power supply
terminal block. Connect the ground cable to the
PE (ground) terminal.
The cable size should conform to those listed below, or a larger size.
∗
When inserting each cable from the left side of the unit (when viewed
from the front of the unit), place the cable along the guide rail in the
electrical equipment box. Then, fasten the cable to the cable anchor
at the bottom of the electrical equipment box by using a tie band etc.
1
2
3
Power cable
insertion hole (f28)
Power cable
insertion hole (
φ
28)
Signal cable
insertion hole (f22)
Signal cable
insertion hole (
φ
22)
For inside of the transformer
box, refer to the transformer
power supply terminal block in
“
Outline of electrical equipment
box
” (page ).
9
AKZJ908
series
AKZJ908-H
Model/Series name
Cable type
AKZJ188,358,458,568
series
Heat-resistant vinyl,
2.0 mm
2
UL1015 AWG#14
(equivalent to 2.0 mm
2
)
2.5 mm
2
(245 IEC53/H05RR-F)
Heat-resistant vinyl,
3.5 mm
2
UL1015 AWG#12
(equivalent to 3.3 mm
2
)
4.0 mm
2
(245 IEC53/H05RR-F)
Heat-resistant vinyl,
5.5 mm
2
UL1015 AWG#10
(equivalent to 5.5 mm
2
)
6.0 mm
2
(245 IEC53/H05RR-F)