When the Oil Cooling Unit does not work well, first check the following points.
If the problem persists, contact DAIKIN Contact Center with information on the following 1), 2) and 3) items.
(For phone/fax number and address of DAIKIN Contact Center, see the back cover.)
1) Machine name (Full Model No.)
2) Manufacture No. (MFG. No.)
3) Condition of the Oil Cooling Unit (as closely as possible)
When the unit operation seems abnormal although no alarm is activated
Item
Condition
Cause
Corrective action
The unit does not run at all.
(The POWER lamp on the control panel is unlit.)
The agitator is running, but the compressor
does not run.
Both the agitator and compressor are running,
but the operating liquid cannot be cooled.
Alarm output operation ([64] or [65]) is different
from that of conventional signal output.
Operation setting cannot be performed.
The agitator does not run.
– – –
1
2
3
4
5
6
1
2
See page .
4
1) The main power supply is OFF, or the power
cable (L1, L2) is disconnected.
2) The compressor restart prevention timer has
been activated (for 30 seconds).
3) The low oil temperature protection device has been
activated. (Inlet oil temperature is 2˚C or lower.)
6) If the exhaust air temperature is almost equal to
the room temperature although the compressor is
in operation, the refrigerant gas is running short.
1) If “---” appears on the data display, the
temperature sensor corresponding to the
selected operation mode is not connected.
2) If “---” instantaneously appears when the [ENT] key
(at the right end of the control panel) is pressed, the
erroneous operation prevention switch is set to ON.
4) The low ambient temperature protection device has
been activated. (Room temperature is –2˚C or lower.)
1) The remote control input ([10]–[11]) is OFF.
1) The compressor is stopped under temperature control.
5) The capacity setting is 0% (Mode 9).
1) There is an obstacle near the air intake/exhaust port.
2) The air filter is clogged.
3) The unit is running under capacity suppressing
control, because the room temperature is high.
1) The alarm output signal connection has been
partially changed.
4) Heat load is large.
5) The temperature setting is high.
2) The unit has been set to the operation lock mode.
(With the factory setting, the operation lock mode is selected.)
Check if the power cable is connected to the
power supply terminal.
Check if the compressor starts after elapse of the
timer preset time.
Check if the compressor normally operates at
5˚C or higher tank liquid temperature.
Check if the compressor normally operates at
0˚C or higher room temperature.
Turn OFF the erroneous operation prevention
switch (SW1) on the control board.
Check the capacity in the operating temperature
range with the catalog, and select a model with
appropriate capacity.
The [60] to [63] outputs are compatible with
conventional models (AKJ6 series). With the 8
series, however, signal operations and
connections of the [64] and [65] outputs have
been changed.
Connect the corresponding temperature sensor.
Cancel the LOCK mode on the control panel.
(See page .)
Check the connection of the remote control input.
Change the operation mode to an appropriate setting.
Remove the obstacle.
Clean the air filter.
Re-fill refrigerant.
Change the temperature setting to an appropriate temperature.
17