6 Configuration
Installation manual
26
EGSAH/X06+10DA9W(G)
Daikin Altherma 3 GEO
4P569811-1 – 2019.02
CAUTION
If there are 2 zones and the emitter types are wrongly
configured, water of high temperature can be sent towards
a low temperature emitter (underfloor heating). To avoid
this:
▪ Install an aquastat/thermostatic valve to avoid too high
temperatures towards a low temperature emitter.
▪ Make sure you set the emitter types for the main zone
[2.7] and for the additional zone [3.7] correctly in
accordance with the connected emitter.
NOTICE
An overpressure bypass valve can be integrated in the
system. Keep in mind that this valve might not be shown
on the illustrations.
6.2.4
Configuration wizard: Backup heater
The backup heater is adapted to be connected to most common
European electricity grids. If the backup heater is available, the
voltage and maximum capacity must be set on the user interface.
Voltage
Depending on how the backup heater is connected to the grid and
what voltage is supplied, the correct value needs to be set. In either
configuration, the backup heater will operate in steps of 1 kW.
#
Code
Description
[9.3.2]
[5‑0D]
▪ 0:
230V, 1ph
▪ 2:
400V, 3ph
Maximum capacity
During normal operation the maximum capacity is:
▪ 3 kW for a 230 V, 1N~ unit
▪ 6 kW for a 400 V, 3N~ unit
The maximum capacity of the backup heater can be limited. The set
value depends on the used voltage (see table below) and is then the
maximum capacity during emergency operation.
#
Code
Description
[9.3.5]
[4-07]
(1)
0~6 kW when voltage is set to 230 V,
1N~
0~9 kW when voltage is set to 400 V,
3N~
(1)
If the value [4-07] is set lower, then the lowest value will be
used in all operation modes.
6.2.5
Configuration wizard: Main zone
The most important settings for the main leaving water zone can be
set here.
Emitter type
Depending on the system water volume and the heater emitter type
of the main zone, heating up or cooling down the main zone can
take longer. The setting
Emitter type
can compensate for a slow
or a quick heating/cooling system during the heat up/cool down
cycle. The target delta T for the main zone depends on this setting.
In room thermostat control,
Emitter type
influences the maximum
modulation of the desired leaving water temperature, and the
possibility for usage of the automatic cooling/heating changeover
based on the indoor ambient temperature.
It is important to set
Emitter type
correctly and in accordance with
your system layout.
#
Code
Description
[2.7]
[2‑0C]
▪ 0:
Underfloor heating
▪ 1:
Fancoil unit
▪ 2:
Radiator
The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:
Description
Space heating setpoint range
0:
Underfloor heating
Maximum 55°C
1:
Fancoil unit
Maximum 65°C
2:
Radiator
Maximum 65°C
Control
Defines how the operation of the unit is controlled. There are 3
possibilities:
#
Code
Description
[2.9]
[C‑07]
▪ 0:
Leaving water
▪ 1:
External room thermostat
▪ 2:
Room thermostat
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:
▪ In
Fixed
LWT setpoint mode, the scheduled actions consist of
desired leaving water temperatures, either preset or custom.
▪ In
Weather dependent
LWT setpoint mode, the scheduled
actions consist of desired shift actions, either preset or custom.
#
Code
Description
[2.1]
N/A
▪ 0:
No
▪ 1:
Yes
6.2.6
Configuration wizard: Additional zone
The most important settings for the additional leaving water zone
can be set here.
Emitter type
For more info about this functionality, see
.
#
Code
Description
[3.7]
[2‑0D]
▪ 0:
Underfloor heating
▪ 1:
Fancoil unit
▪ 2:
Radiator
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
"6.2.5 Configuration wizard: Main zone" on
.
#
Code
Description
[3.9]
N/A
▪ 0:
Leaving water
if the control type
of the main zone is
Leaving water
.
▪ 1:
External room thermostat
if the
control type of the main zone is
External room thermostat
or
Room
thermostat
.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Also see
"6.2.5 Configuration wizard: Main zone" on
.