8
|
Configuration
Installer reference guide
117
EPGA11~ EAV23DA6V
Daikin Altherma 3 H F
4P606487-1 – 2019.12
Setpoint range
Only applicable in room thermostat control.
To save energy by preventing overheating or undercooling the room, you can limit
the range of the room temperature for heating and/or cooling.
NOTICE
When adjusting the room temperature ranges, all desired room temperatures are
also adjusted to guarantee they are between the limits.
#
Code
Description
[1.5.1]
[3-07]
Heating minimum
[1.5.2]
[3-06]
Heating maximum
[1.5.3]
[3-09]
Cooling minimum
[1.5.4]
[3-08]
Cooling maximum
Room sensor offset
Only applicable in room thermostat control.
To calibrate the (external) room temperature sensor, give an offset to the value of
the room thermistor as measured by the user interface used as room thermostat
or by the external room sensor. The setting can be used to compensate for
situations where the user interface used as room thermostat or the external room
sensor cannot be installed at the ideal location.
See
"5.7 Setting up an external temperature sensor"
#
Code
Description
[1.6]
[2-0A]
Room sensor offset
(user interface used as
room thermostat): Offset on the actual room
temperature measured by the user interface
used as room thermostat.
▪
–5°C~5°C, step 0.5°C
[1.7]
[2-09]
Room sensor offset
(external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪
–5°C~5°C, step 0.5°C
8.4.3 Main zone
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone
.
See
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪
In
Fixed
LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.