background image

6 Configuration

Installation manual

20

ETVH/9W(G)

Daikin Altherma 3 H HT F

4P586454-1 – 2019.07

Capacity step 1

#

Code

Description

[9.3.4]

[6‑03]

▪ The  capacity  of  the  first  step  of  the

backup heater at nominal voltage.

Additional capacity step 2

#

Code

Description

[9.3.5]

[6‑04]

▪ The  capacity  difference  between  the

second  and  first  step  of  the  backup
heater  at  nominal  voltage.  Nominal
value  depends  on  backup  heater
configuration.

6.2.5

Configuration wizard: Main zone

The most important settings for the main leaving water zone can be
set here.

Emitter type

Depending on the system water volume and the heater emitter type
of  the  main  zone,  heating  up  or  cooling  down  the  main  zone  can
take longer. The setting 

Emitter  type

 can compensate for a slow

or  a  quick  heating/cooling  system  during  the  heat  up/cool  down
cycle. The target delta T for the main zone depends on this setting.

In room thermostat control, 

Emitter  type

 influences the maximum

modulation  of  the  desired  leaving  water  temperature,  and  the
possibility  for  usage  of  the  automatic  cooling/heating  changeover
based on the indoor ambient temperature.

It is important to set 

Emitter type

 correctly and in accordance with

your system layout.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 70°C

Fixed 10°C

NOTICE

For  radiators,  the  average  emitter  temperature  will  be
lower  compared  to  underfloor  heating,  due  to  the  fixed
delta T of 10°C. To compensate, you can:

▪ Increase  the  weather  dependent  curve  desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Defines  how  the  operation  of  the  unit  is  controlled.  There  are  3
possibilities:

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

In 

Fixed

  mode,  the  desired  leaving  water  temperature  does  NOT

depend on the outdoor ambient temperature.

In 

WD  heating,  fixed  cooling

  mode,  the  desired  leaving  water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does NOT depend on the outdoor ambient temperature for cooling

In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather dependent operation, the user has the possibility to shift the
water temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

6.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"6.2.5  Configuration

wizard: Main zone" 

[

4

 20].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Summary of Contents for Altherma 3 H HT F Series

Page 1: ...manual Daikin Altherma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18DA6V G ETVH16S23DA6V G ETVH16S18DA9W G ETVH16S23DA9W G ETVX16S18DA6V G ETVX16S23DA6V G ETVX16S18DA9W G ETV...

Page 2: ...ou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u...

Page 3: ...up heater 19 6 2 5 Configuration wizard Main zone 20 6 2 6 Configuration wizard Additional zone 20 6 2 7 Configuration wizard Tank 21 6 3 Weather dependent curve 21 6 3 1 What is a weather dependent c...

Page 4: ...liance or an operating electric heater 3 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoor installation only and for the following ambient temperatures Space...

Page 5: ...wing cases 3 2 2 To lower the switch box on the indoor unit 45 3 3 2 To connect the drain hose to the drain 46 When you need access to the high voltage switch box 2 T25 5 If you need access to the hig...

Page 6: ...in hose to the drain See 3 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into position 4 Adjust the height of the leveling feet to compensate for floor irregularities The maxim...

Page 7: ...the water piping 4 2 1 To connect the water piping 1 Connect the O rings and shut off valves to the outdoor unit water connection pipes of the indoor unit 2 Connect the outdoor unit field piping to t...

Page 8: ...ms galvanic corrosion cells that cause severe damage to the system Therefore it is important that the water treatment is correctly executed by a qualified water specialist a glycol with corrosion inhi...

Page 9: ...taps after all air is purged 4 Check for water leaks 4 2 6 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and...

Page 10: ...0 75 1 25 mm Must be sheathed Maximum length 200 m See below LAN adapter System requirements LAN adapter System requirements The requirements posed on the Daikin Altherma system depend on the LAN ada...

Page 11: ...1Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required...

Page 12: ...ual to Zmax d 6T1 Connect the backup heater power supply as follows X6M F1B Q1DI a b a Factory mounted cable connected to the backup heater contactor inside the switch box K5M b Field wiring see table...

Page 13: ...with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Open the following see 3 2 1 To open the indoor unit 44...

Page 14: ...rm output 3 Wire between X2M and A4P A4P Installation of EKRP1HB is required A Y1 7 B A B 7 9 X2M A4P Y1 YC X1M a b a Installation of EKRP1HB is required b Prewiring between X2M 7 9 and Q1L thermal pr...

Page 15: ...1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below A X1 X2 L N B A B A4P X2M...

Page 16: ...3 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary trip...

Page 17: ...u can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applic...

Page 18: ...t cannot be adjusted Backup heater type The backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units wit...

Page 19: ...E 0D Glycol Filled system Is the system filled with glycol 0 No 1 Yes 6 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids I...

Page 20: ...ontrol Defines how the operation of the unit is controlled There are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless t...

Page 21: ...op can be programmed This feature puts a stop to tank heating even if the setpoint has NOT been reached Only program a storage stop when tank heating is absolutely undesirable Code Description 5 2 6 0...

Page 22: ...eaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature i...

Page 23: ...mum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for that zone or for the tank When the maximum or minimum...

Page 24: ...in external room thermostat control For more info about the functionality see 6 4 1 Main zone 423 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contac...

Page 25: ...9 B Sensors External sensor Ext amb sensor offset Averaging time 9 C Bivalent Bivalent Boiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limi...

Page 26: ...islation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply panel and the indoor unit Between the indoor unit and the valves if applicabl...

Page 27: ...e list Example Pump 4 Select OK to confirm Result The actuator test run starts It stops automatically when done 30 min To stop the test run manually 1 In the menu go to Stop test run 2 Select OK to co...

Page 28: ...ask him her to keep it for future reference Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual Explain the user how to properly operate the system...

Page 29: ...ter cold water IN loose nut 3 4 b2 Domestic hot water hot water OUT loose nut 3 4 c1 Water IN connection c2 Water OUT connection d Pump e Backup heater f Shut off valve male female 1 g Expansion vesse...

Page 30: ...wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box...

Page 31: ...ed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact 16 V DC detection voltage supplied by PCB English Translati...

Page 32: ...e 2 core 2 core 3 core R2T External sensor floor or ambient Only for KRTETS signal 2 core 3m included A13P P1 P2 LAN adapter A14P P1 P2 user interface Only for Human Comfort Interface Only for KRTR wi...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...4P586454 1 2019 07 Copyright 2019 Daikin 4P586454 1 0000000U...

Reviews: