To check for non-condensables in the refrigerant
circuit
Prerequisite:
Turn OFF the unit via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
1
Wait for the refrigerant to reach the outdoor temperature.
2
Connect a manometer to the service port.
3
Measure the pressure of the refrigerant. The measured
pressure MUST be in line with the expected pressure at outdoor
temperature.
4
If the measured pressure is higher than the expected pressure
(at outdoor temperature), other non‑condensables are mixed in
the refrigerant.
Any non‑condensables found
in the refrigerant circuit?
Action
Yes
To replace the refrigerant, see
"3.2.2 Repair procedures" on
page 93
.
No
of the
refrigerant circuit and continue
with the next procedure.
To perform a pressure test of the refrigerant circuit
1
Perform a pressure test in line with local legislation.
CAUTION
Perform a pressure test only when leaks are expected.
Is the pressure in the
refrigerant circuit correct?
Action
Yes
of the
refrigerant circuit and continue
with the next procedure.
No
Replace the leaking part of the
refrigerant circuit, see
"3.2.2 Repair procedures" on
page 93
.
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
3.2.2
Repair procedures
To open the stop valve of the refrigerant circuit
Prerequisite:
Remove the required plate work, see
.
1
Remove the caps.
a
a
c
b
a
Cap
b
Liquid stop valve
c
Gas stop valve
2
Completely open the stop valve by screwing the stop valve
screw counterclockwise.
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of
the specific error and continue
with the next procedure.
To replace the clogged/leaking part of the
refrigerant circuit
1
See the correct procedure for the component that needs to be
repaired. See also
"Repair information" on page 94
for more
details.
Is the problem solved?
Action
Yes
No further actions required.
No
of the
refrigerant circuit and continue
with the next procedure.
To recuperate the refrigerant
Prerequisite:
Turn OFF the unit via the user interface.
1
Manually open the expansion valve.
2
Connect the vacuum pump, manifold, recovery unit, and
refrigerant bottle to the service port of the refrigerant circuit as
shown below.