2 Components
Service manual
77
EBLQ+EDLQ011~W1 + EBLQ+EDLQ011~0W1
+ EK(2)CB EKMB9W1
Daikin Altherma – Monobloc
ESIE18-04 – 2019.02
2.19
Plate work
INFORMATION
If required also remove the hydrobox for easier access.
2.19.1
To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
1×
2×
2×
6
5
1
3
4
2
8
9
7
2.19.2
To open the switch box cover of the
outdoor unit
3×
2.19.3
To open the control box
1
1
2
2×
WARNING
The screws are delivered with toothed lock washers.
ALWAYS use toothed lock washers, also when the screws
need to be replaced. Failure to follow this warning may
result in electric shock.
INFORMATION
The holes in the front plate are for the connection of the
user interface to the control box. If you do NOT connect
the user interface to the control box, do NOT remove the
plugs from the holes.
2.19.4
To open the option box
1
1
2
2×
WARNING
The screws are delivered with toothed lock washers.
ALWAYS use toothed lock washers, also when the screws
need to be replaced. Failure to follow this warning may
result in electric shock.
INFORMATION
Do NOT remove the plugs from the front plate of the option
box.
2.19.5
To remove the hydrobox
INFORMATION
This procedure is just an example and may differ on some
details for your actual unit.
Prerequisite:
Turn OFF the unit via the user interface.